ELECTRIC
AIR CONDITIONER
Model 593C (60 Hz)
Sizes 018 thru 060
WEATHER-PROTECTIVE CABINET—Steel is galvanized and
coated with a layer of zinc phosphate. A coat of modified poly-
ester powder coating is then applied and baked-on, providing
each unit with a hard, smooth finish that will last for many years.
All screws on cabinet exterior are ceramic coated for a long-
lasting, rust-resistant, quality appearance.
HEAVY DUTY INLET GRILLE—The DuraGuard™ coil protec-
tor, made of a coated steel wire grid with vertical 3/8 in. spacing,
is designed to help protect the coil from inclement weather, van-
dalism, and incidental damage. It provides protection while not
restricting airflow and maintaining ease of coil inspection and
cleaning.
TOTALLY ENCLOSED FAN MOTOR—Means greater reliability
under adverse weather conditions and dependable perfor-
mance for many years. The permanent-split-capacitor type
motor was designed for optimum efficiency. Then the motor was
tested and qualified under extreme conditions to help ensure
the greatest reliability.
UNIT DESIGN—Copper tube, enhanced aluminum fin coil is
designed for optimum heat transfer. Vertical air discharge car-
ries sound and hot condenser air up and away from adjacent
patio areas and foliage. Heat pump-style drain pan for easy
removal of water, dirt, and leaves.
BRYANT’S AEROQUIET SYSTEM—Extremely low operating
sound is the result of special attention to the air moving through
the outdoor unit, and a specially designed sound enclosure sur-
rounding the compressor to eliminate sound transmission to the
rest of the systems.
APPLICATION VERSATILITY—The 593C can be combined
with a wide variety of evaporator coils and blower packages to
provide quiet, dependable comfort. Unit can be installed on a
roof or at ground level on a slab.
EXTERNAL SERVICE VALVES—Both service valves are
brass, front seating type with sweat connections. Valves are
externally located so refrigerant tube connections can be made
quickly and easily. Each valve has a service port for ease of
checking operating refrigerant pressures.
EASY SERVICEABILITY—One access panel provides access
to electrical controls and compressor. Removal of wire dome
gives access to fan motor and removal of the top gives access
to the coil. For improved serviceability, all models are equipped
with a compressor terminal plug.
COMPRESSOR PROTECTION—Each model is protected with
internal temperature- and current-sensitive overloads. An inter-
nal pressure relief valve provides high-pressure protection to
the refrigerant system.
LIMITED WARRANTY—Standard 5-year warranty on all parts,
with an additional 10-year warranty on compressor.
Model 593C Energy-Efficient Air Conditioners incor-
porate innovative technology to provide quiet, reliable
cooling performance. Built into these units are the fea-
tures most desired by homeowners today. Standard
SEER ratings of 10.0 can reach as high as 11.2 when
combined with specific Bryant equipment. All models
are listed with ARI, UL (U.S. and Canada), and CEC.
AVAILABLE OPTIONS
ELECTRICAL RANGE—All units are offered in 208–
230v single phase.
WIDE RANGE OF SIZES—Available in 7 nominal
sizes from 018 through 060 to meet the needs of resi-
dential and light commercial applications.
Form No. PDS 593C.18.7
RECOMMENDED TUBE DIAMETERS
LIQUID TUBE DIAMETER (IN.)
VAPOR TUBE DIAMETER (IN.)
UNIT
SIZE
0 to 50 Ft
Tube Length
0 to 50 Ft
Tube Length
Long-Line Applications*
(Maximum Diameter)
Long-Line Applications*
018, 024
030, 036
042, 048
060
5/8
3/4
7/8
3/4
7/8
1-1/8
1-1/8
3/8
3/8
1-1/8
* For tube sets between 50 and 175 ft, consult Residential Split System Long-Line Application Guideline.
CHECK-FLO-RATER® PISTON
PISTON*
UNIT SIZE—SERIES
018-C, D
024-C, D
030-C, D
036-C, D
042-C, D
048-C
IDENTIFICATION NO.
55
57
67
73
78
82
96
060-C
* Piston listed is for any approved non-capillary tube coil combination. Piston is
shipped with outdoor unit and must be installed in an approved indoor coil.
REGISTERED QUALITY SYSTEM
CERTIFICATION APPLIES ONLY
WHEN THE COMPLETE SYSTEM
IS LISTED WITH ARI.
—3—
SPECIFICATIONS
UNIT SIZE
018-C, D
024-C, D
030-C, D
036-C, D
Operating Weight (Lb)
137
143
161
169
ELECTRICAL
Unit Volts—Hertz—Phase
Operating Voltage Range*
Compressor— Rated Load Amps
Locked Rotor Amps
208–230—60—1
197—253
8.6
49.0
0.5
11.3
14
14
62
66
15
10.9
56.0
0.5
14.1
14
14
50
53
20
13.7
75.0
0.8
17.9
14
14
42
44
25
15.0
82.0
1.4
20.2
12
12
57
60
30
Condenser Fan Motor—Full Load Amps
Min Unit Ampacity for Wire Sizing
Min Wire Size (75°C Copper) AWG†
Min Wire Size (60°C Copper) AWG†
Max Wire Length (Ft) (75°C Copper)‡
Max Wire Length (Ft) (60°C Copper)‡
Max Branch Circuit Fuse Size**
COMPRESSOR and REFRIGERANT
Compressor—Manufacturer and Type
Temperature and Current Protection
Refrigerant—Type and Amount (Lb)††
CONDENSER COIL and FAN
Coil Face (Sq Ft)
Copeland Reciprocating
Internal Line Break
R-22 and 3.88
R-22 and 4.44
R-22 and 4.63
R-22 and 5.50
7.2
7.2
8.8
10.9
Fins per In.—Rows—Circuits
Fan Motor—HP, Type, and RPM
Volts—Hertz—Phase
20—1—1
25—1—1
25—1—2
1/10 PSC and 1100
25—1—2
1/4 PSC and 1100
1/12 PSC and 1100
208/230—60—1
Condenser Airflow (CFM)
OPTIONAL EQUIPMENT
Support Feet
Coastal Filter
Time Delay Relay
Cycle Protector
Crankcase Heater
Start Assist—Capacitor/Relay Type
Start Assist—PTC Type
Sound Hood
1900
1900
2100
2600
KSASF0101AAA
KAACF0701SML
KAATD0601TDR
KSACY0101AAA
KAACH1001AAA
KSAHS1001AAA
KAACS0201PTC
KSASH1101COP
KSASH1201COP
TXV Kit (RPB)
KAATX0201RPB
KAATX0301RPB
KAATX0401RPB
KAATX0501RPB
TXV Kits (Hard Shutoff)
Low-Pressure Switch
High-Pressure Switch
KSATX0601HSO
KAALP0101LPS
KSAHI0101HPS
P502-8083S (RCD)
KAAFT0101AAA
KAALS0101LLS
KAAWS0101AAA
KSALA0201R22
32LT660004 (RCD)
HC34GE232 (RCD)
Filter Drier
Evaporator Freeze Thermostat**
Liquid-Line Solenoid Valve
Winter Start Control**
Low-Ambient Kit
MotorMaster® Control††
Ball Bearing Fan Motor
Thermostat, Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
Thermostat, Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
Builder’s Thermostat, Manual
Changeover, Non-Programmable,
°F/°C, 1-Stage Heat, 1-Stage Cool
TSTATBBNAC01-B
TSTATBBPAC01-B
TSTATBBBAC01-B
Thermidistat™ Control—Programmable/
Non-Programmable Thermostat with
Humidity Control
TSTATBBPRH01-B
TSTATBBSEN01-B
Outdoor Air Temperature Sensor
Backplate for Non-Programmable
Thermostat
Backplate for Programmable Thermostat
TSTATXXNBP01
TSTATXXPBP01
TSTATXXBBP01
Backplate for Builder’s Thermostat
Thermostat Conversion Kit (4 to 5 wire)
— 10 Pack
TSTATXXCNV10
See notes on page 5.
—4—
SPECIFICATIONS Continued
UNIT SIZE
042-C, D
048-C
060-C
Operating Weight (Lb)
206
199
217
ELECTRICAL
Unit Volts—Hertz—Phase
Operating Voltage Range*
Compressor— Rated Load Amps
Locked Rotor Amps
208–230—60—1
197—253
24.4
140.0
1.4
31.9
10
19.0
105.0
1.4
25.2
10
10
73
77
40
28.8
165.0
1.4
37.4
8
8
78
82
60
Condenser Fan Motor—Full Load Amps
Min Unit Ampacity for Wire Sizing
Min Wire Size (75°C Copper) AWG†
Min Wire Size (60°C Copper) AWG†
Max Wire Length (Ft) (75°C Copper)‡
Max Wire Length (Ft) (60°C Copper)‡
Max Branch Circuit Fuse Size**
COMPRESSOR and REFRIGERANT
Compressor—Manufacturer and Type
Temperature and Current Protection
Refrigerant—Type and Amount (Lb)††
CONDENSER COIL and FAN
Coil Face (Sq Ft)
Fins per In.—Rows—Circuits
Fan Motor—HP, Type, and RPM
Volts—Hertz—Phase
Condenser Airflow (CFM)
OPTIONAL EQUIPMENT
Support Feet
8
59
97
50
Copeland Reciprocating
Internal Line Break
R-22 and 5.51
Millennium Scroll
R-22 and 7.63
Millennium Scroll
Internal Line Break and Dome Thermostat
R-22 and 10.63
12.2
20—1—2
15.2
25—1—3
1/4 PSC and 1100
208/230—60—1
3000
18.3
25—1—4
KSASF0101AAA
KAACF0801MED
KAATD0101TDR
KSACY0101AAA
Coastal Filter
Time Delay Relay
Cycle Protector
Crankcase Heater
Standard
KSAHS1301AAA
KAACH1201AAA
KSAHS1601AAA
Start Assist—Capacitor/Relay Type
Start Assist—PTC Type
Sound Hood
TXV Kit (RPB)
TXV Kits (Hard Shutoff)
Low-Pressure Switch
High-Pressure Switch
Filter Drier
Evaporator Freeze Thermostat**
Liquid-Line Solenoid Valve
Winter Start Control**
KAACS0201PTC
KAATX0601RPB
KSASH1201COP
KAATX0501RPB
KSATX0601HSO
KSASH2001CYL
KSATX0701HSO
KAATX0701RPB
KAALP0101LPS
KSAHI0101HPS
P502-8163S (RCD)
KAAFT0101AAA
KAALS0101LLS
KAAWS0101AAA
KSALA0201R22
32LT660004 (RCD)
HC40GE232 (RCD)
Low-Ambient Kit
MotorMaster® Control††
Ball Bearing Fan Motor
Thermostat, Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
Thermostat, Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
Builder’s Thermostat, Manual
Changeover, Non-Programmable,
°F/°C, 1-Stage Heat, 1-Stage Cool
TSTATBBNAC01-B
TSTATBBPAC01-B
TSTATBBBAC01-B
Thermidistat™ Control—Programmable/
Non-Programmable Thermostat with
Humidity Control
TSTATBBPRH01-B
TSTATBBSEN01-B
Outdoor Air Temperature Sensor
Backplate for Non-Programmable
Thermostat
Backplate for Programmable Thermostat
TSTATXXNBP01
TSTATXXPBP01
TSTATXXBBP01
Backplate for Builder’s Thermostat
Thermostat Conversion Kit (4 to 5 wire)
— 10 Pack
TSTATXXCNV10
* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors per the NEC (ANSI/NFPA 70) Article
336-26. If other than uncoated (non-plated), 60° or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
** Fan motor with ball bearings required. See Low-ambient controller Installation Instructions for application.
NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.
—5—
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
1. Ball Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.
2. Coastal Filter
A filter designed to protect the condenser coil from salt damage without restricting airflow through the outdoor coil.
SUGGESTED USE: Geographic areas prone to salt spray. Used to meet job specifications where added coil protection is required.
3. Compressor Start Assist—Capacitor/Relay Type
Start capacitor and start relay gives ‘‘hard’’ boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.
Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil.
Installations where Liquid-Line Solenoid Valve has been added.
4. Compressor Start Assist—PTC Type
Solid-state electrical device which gives a ‘‘soft’’ boost to compressor at each start-up.
SUGGESTED USE: Installations with marginal power supply.
5. Crankcase Heater
An electric resistance heater which mounts to the base of compressor to keep lubricant warm during off cycles. Improves compressor lubrication on
restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 50 ft.
When unit will be operated below 55°F (12.8°C) outdoor air temperature. Use with Low-Ambient Controller.
All commercial installations.
6. Cycle Protector
Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has
been interrupted for any reason, including normal room thermostat cycling.
SUGGESTED USE: Installations in areas where power interruptions are frequent.
Where user is likely to ‘‘play’’ with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
High rise applications.
7. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: All units where Low-Ambient Controller has been added.
8. Filter Drier
A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow.
SUGGESTED USE: All split-system air conditioners.
9. High-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 10
psig and resets at 298 20 psig. Provides additional protection against compressor damage due to loss of outdoor airflow. To prevent rapid compressor
recycling, Cycle Protector can be used with this switch.
SUGGESTED USE: Installations exposed to very ‘‘dirty’’ outdoor air.
Installations where condenser inlet air temperature exceeds 125°F (51.7°C).
10. Liquid-Line Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration), which stops and starts refrigerant
liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.
Note: Compressor Start Assist—Capacitor/Relay Type must also be used. Do not use with hard shutoff TXV.
SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
In certain long line applications. Refer to Long-Line Application Guideline.
11. Low-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on low side of refrigerant circuit. Cycles compressor off if refrigerant pressure drops to about 27
psig. Prevents indoor coil freeze-up due to loss of indoor airflow. Also, provides additional protection against compressor damage due to loss of refrigerant
charge. To prevent rapid compressor recycling. Compressor Cycle Protector can be used with this switch.
SUGGESTED USE: Where indoor coil is exposed to ‘‘dirty’’ air.
All commercial installations.
12. MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing
temperature during operation in cooling mode only. For outdoor temperatures down to –20°F, it maintains condensing temperature at 100°F 10°F.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F.
All commercial installations.
13. Outdoor Air Temperature Sensor
A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.
SUGGESTED USE: All corporate programmable thermostats.
14. Sound Hood
Wrap-around sound attenuation cover for the compressor. Reduces the sound level by about 2 decibels.
SUGGESTED USE: Unit installed closer than 15 ft to quiet areas—bedrooms, etc.
Unit installed between 2 houses less than 10 ft apart.
15. Support Feet
Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base;
minimizes corrosion.
SUGGESTED USE: Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
16. Thermostatic Expansion Valve (TXV) Kits
A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the
evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB type valves are available. Do not use hard shutoff
TXV with Liquid-Line Solenoid Valve.
SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
Required for use on all zoning systems.
—6—
ACCESSORY DESCRIPTION AND USE (Listed Alphabetically) Continued
17. Time Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
18. Winter Start Control
An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low load
conditions.
SUGGESTED USE: All air conditioners where Low-Ambient Controller has been added.
ACCESSORY USAGE GUIDELINE
REQUIRED FOR
LOW-AMBIENT
APPLICATIONS
(Below 55°F)
REQUIRED FOR
LONG-LINE
REQUIRED FOR
SEA COAST
APPLICATIONS*
(Over 50 Ft)
APPLICATIONS
(Within 2 Miles)
ACCESSORY
Crankcase Heater
Evaporator Freeze Thermostat
Winter Start Control
Accumulator
Yes
Yes
Yes†
No
Yes
No
No
No
No
No
No
No
Compressor Start Assist
Capacitor and Relay
Yes
Yes
No
MotorMaster® Control
or
Low-Ambient Pressure Switch
Yes
No
No
Wind Baffle
Coastal Filter
Support Feet
See Low-Ambient Instructions
No
No
No
No
Yes
No
Recommended
Recommended
Liquid-Line Solenoid Valve
See Long-Line
Application
Guideline
or
No
No
Hard Shutoff TXV
Ball Bearing Fan Motor
Yes‡
No
No
*
For tubing line sets greater than 50 ft and/or 20 ft vertical differential, refer to Residential Split-system Long-Line Application Guideline and Service Manual.
† Only when low-pressure switch is used.
‡ Required for Low-Ambient Controller (full modulation feature) and MotorMaster® Control only.
SOUND POWER (dBA)
Sound
Level
(dBA)
OCTAVE BAND CENTER FREQUENCY (Hz)
Unit
Size
125
54.0
53.0
53.5
57.0
62.5
63.0
61.5
250
63.5
69.0
64.0
65.5
69.0
71.0
69.5
500
66.0
69.5
66.5
71.0
72.0
71.0
71.0
1000
66.0
71.0
69.5
75.0
75.0
72.0
74.5
2000
65.0
68.5
69.0
71.0
72.0
73.5
70.0
4000
62.5
64.5
65.0
67.5
69.5
68.0
69.0
8000
55.5
60.5
58.5
62.0
62.5
63.5
66.0
018-C, D
024-C, D
030-C, D
036-C, D
042-C, D
048-C
76
78
80
80
80
82
82
060-C
—7—
COMBINATION RATINGS
FACTORY-
BRYANT GAS
FURNACE OR
ACCESSORY
TDR†
TOT.
CAP.
BTUH
SUPPLIED
ENHANCE-
MENT
UNIT
SIZE-SERIES
INDOOR
MODEL
STANDARD
RATING
ACCESSORY
TXV‡
CC5A/CD5AA018*
CC5A/CD5AA024
CC5A/CD5AW024
CE3AA024
17,200
17,800
17,800
18,000
18,000
17,800
17,200
17,800
17,800
17,000
18,000
18,000
17,000
18,000
17,600
18,000
18,000
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
TDR
10.00
10.50
10.50
10.50
10.50
10.50
10.00
10.50
10.50
10.00
10.50
10.50
10.00
10.20
10.20
12.00
12.00
10.50
11.00
11.00
11.00
11.00
11.00
10.50
11.00
11.00
—
10.50
11.00
11.00
11.00
11.00
11.00
10.50
11.00
11.00
10.00
10.50
—
CF5AA024
CK3BA024
CK5A/CK5BA018
CK5A/CK5BA024
CK5A/CK5BW024
F(A,B)4(A,B)NF018
F(A,B)4(A,B)NF024
FC4(B,C)NF024
FF1DNA018
TDR
—
TDR & TXV
TDR
—
—
10.50
10.50
10.60
—
FF1DNA024
TDR
—
FG3AA024
NONE
TDR & TXV
TDR & TXV
10.60
—
FK4(C,D)NF001
FK4(C,D)NF002
—
—
COILS + 315(A,J)AV036070 VARIABLE-SPEED FURNACE
018-C, D
CC5A/CD5AA018
CC5A/CD5AA024
CC5A/CD5AW024
CE3AA024
17,200
17,600
17,600
17,600
17,600
17,200
17,600
17,600
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
10.35
10.65
10.65
10.65
10.85
10.6
11.5
11.5
11.5
11.5
11
11.5
11.5
11.5
11.5
11
CK3BA024
CK5A/CK5BA018
CK5A/CK5BA024
CK5A/CK5BW024
11.5
11.5
11.5
11.5
10.85
10.85
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
17,600 NONE 11.00
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CD5A/CD5BA018
—
11.00
CC5A/CD5AA018
CK3BA024
CK5A/CK5BW024
17,600
17,600
17,600
NONE
NONE
NONE
11.00
11.50
11.50
—
—
—
11.00
11.50
11.50
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5AA018
CK3BA024
CK5A/CK5BW024
17,600
17,600
17,600
NONE
NONE
NONE
11.00
11.50
11.50
—
—
—
11.00
11.50
11.50
CC5A/CD5AA024*
CC5A/CD5AA030
CC5A/CD5AW024
CC5A/CD5AW030
CE3AA024
23,000
23,000
23,000
23,000
23,200
23,400
23,000
23,000
23,000
23,000
23,000
23,000
23,000
23,000
23,200
23,000
23,400
23,000
23,400
22,400
24,000
24,000
24,000
NONE
10.00
10.00
10.00
10.10
10.00
10.10
10.10
10.00
10.00
10.00
10.00
10.00
10.00
10.00
10.20
10.00
10.20
10.00
10.00
10.00
11.50
11.50
11.50
10.20
10.50
10.20
10.50
10.20
10.50
10.50
10.20
10.50
10.20
10.50
10.20
10.50
—
10.20
10.50
10.20
10.50
10.20
10.50
10.50
10.20
10.50
10.20
10.50
10.20
10.50
10.00
10.20
—
NONE
NONE
NONE
NONE
CE3AA030
NONE
CF5AA024
NONE
CK3BA024
NONE
CK3BA030
NONE
CK5A/CK5BA024
CK5A/CK5BA030
CK5A/CK5BW024
CK5A/CK5BW030
F(A,B)4(A,B)NF024
F(A,B)4(A,B)NF030
FC4(B,C)NF024
FC4(B,C)NF030
FF1DNA024
NONE
NONE
NONE
NONE
TDR
TDR
—
TDR & TXV
TDR & TXV
TDR
—
—
—
—
10.20
10.20
10.20
—
—
—
FF1DNA030
TDR
NONE
—
FG3AAA024
10.20
—
FK4(C,D)NF001
FK4(C,D)NF002
FK4(C,D)NF003
TDR & TXV
TDR & TXV
TDR & TXV
—
—
COILS + 315(A,J)AV036070 VARIABLE-SPEED FURNACE
CC5A/CD5AA024
CC5A/CD5AA030
CC5A/CD5AW024
CC5A/CD5AW030
CE3AA024
22,200
22,400
22,200
22,400
22,200
22,400
22,200
22,400
22,200
22,400
22,200
22,400
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
9.85
10
9.85
10
024-C, D
9.9
10.05
10
CE3AA030
CK3BA024
CK3BA030
CK5A/CK5BA024
CK5A/CK5BA030
CK5A/CK5BW024
CK5A/CK5BW030
10
10
10
10
10
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5AA024
CK3BA024
22,600
22,600
23,200
23,200
NONE
NONE
NONE
NONE
11.00
11.00
11.20
11.20
—
—
—
—
11.00
11.00
11.20
11.20
CK3BA030
CK5A/CK5BW030
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5AA024
CK3BA024
22,600
22,600
23,200
22,600
23,200
NONE
NONE
NONE
NONE
NONE
11.00
11.00
11.20
11.00
11.20
—
—
—
—
—
11.00
11.00
11.20
11.00
11.20
CK3BA030
CK5A/CK5BW024
CK5A/CK5BW030
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5AA024
CK3BA024
22,600
22,600
23,200
22,600
23,200
NONE
NONE
NONE
NONE
NONE
11.00
11.00
11.20
11.00
11.20
—
—
—
—
—
11.00
11.00
11.20
11.00
11.20
CK3BA030
CK5A/CK5BW024
CK5A/CK5BW030
See notes on page 14.
—8—
COMBINATION RATINGS Continued
FACTORY-
BRYANT GAS
FURNACE OR
ACCESSORY
TDR†
TOT.
CAP.
BTUH
SUPPLIED
ENHANCE-
MENT
UNIT
SIZE-SERIES
INDOOR
MODEL
STANDARD
RATING
ACCESSORY
TXV‡
CC5A/CD5AA030*
CC5A/CD5AA036
CC5A/CD5AW030
CD5AW036
28,600
29,000
28,600
29,000
28,400
29,000
29,000
28,600
29,000
28,600
29,000
27,000
28,600
29,000
28,200
28,800
28,400
28,800
28,400
28,400
29,000
29,600
29,600
29,600
30,0000
NONE
NONE
10.00
10.10
10.00
10.10
10.00
10.10
10.10
10.00
10.10
10.00
10.10
10.10
10.00
10.10
10.00
10.20
10.00
10.20
10.00
10.00
10.20
11.00
11.00
11.20
11.50
10.20
10.50
10.20
10.50
10.20
10.50
10.50
10.20
10.50
10.20
10.50
10.50
10.20
10.50
—
10.20
10.50
10.20
10.50
10.20
10.50
10.50
10.20
10.50
10.20
10.50
10.50
10.20
10.50
10.00
10.20
—
NONE
NONE
CE3AA030
NONE
CE3AA036
NONE
CF5AA036
NONE
CK3BA030
NONE
CK3BA036
NONE
CK5A/CK5BA030
CK5A/CK5BA036
CK5A/CK5BN036
CK5A/CK5BW030
CK5A/CK5BW036
F(A,B)4(A,B)NF030
F(A,B)4(A,B)NF036
FC4(B,C)NF030
FC4(B,C)NF036
FD3(A,B)NA030
FF1DNA030
NONE
NONE
NONE
NONE
NONE
TDR
TDR
—
TDR & TXV
TDR & TXV
NONE
—
—
—
—
10.00
10.00
10.50
—
TDR
NONE
TDR & TXV
TDR & TXV
TDR & TXV
TDR & TXV
—
FG3AAA036
10.50
—
FK4(C,D)NF001
FK4(C,D)NF002
FK4(C,D)NF003
FK4(C,D)NF005
—
—
—
—
—
—
COILS + 315(A,J)AV036070 VARIABLE-SPEED FURNACE
CC5A/CD5AA030
CC5A/CD5AA036
CC5A/CD5AW030
CE3AA030
28,000
29,000
28,000
28,000
28,600
28,000
29,000
28,000
29,000
29,000
28,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
9.75
10.05
9.75
9.85
9.9
9.75
10.05
9.75
10.05
10.05
9.75
CE3AA036
CK3BA030
CK3BA036
CK5A/CK5BA030
CK5A/CK5BA036
CK5A/CK5BT036
CK5A/CK5BW030
COILS + 315(A,J)AV048090 VARIABLE-SPEED FURNACE
CC5A/CD5AA030
CC5A/CD5AA036
CC5A/CD5AW030
CC5A/CD5AW036
CE3AA030
28,000
29,000
28,000
29,000
28,000
28,600
28,000
29,000
28,000
29,000
28,000
29,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
9.85
10.15
9.85
10.15
9.95
030-C, D
CE3AA036
10.05
9.85
CK3BA030
CK3BA036
CK5A/CK5BA030
CK5A/CK5BA036
CK5A/CK5BW030
CK5A/CK5BW036
10.15
9.85
10.15
9.85
10.15
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5AA030
CK3BA030
29,000
29,000
29,000
29,000
29,000
NONE
NONE
NONE
NONE
NONE
11.00
10.50
10.50
10.50
10.50
—
—
—
—
—
11.00
10.50
10.50
10.50
10.50
CK3BA036
CK5A/CK5BW030
CK5A/CK5BW036
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5AA030
CK3BA030
29,000
29,000
29,000
29,000
27,000
29,000
NONE
NONE
NONE
NONE
NONE
NONE
11.00
10.50
10.50
10.50
10.50
10.50
—
—
—
—
—
—
11.00
10.50
10.50
10.50
10.50
10.50
CK3BA036
CK5A/CK5BA036
CK5A/CK5BN036
CK5A/CK5BW030
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5AA030
CK3BA030
29,000
29,000
29,000
29,000
29,000
NONE
NONE
NONE
NONE
NONE
11.00
10.50
10.50
10.50
10.50
—
—
—
—
—
11.00
10.50
10.50
10.50
10.50
CK3BA036
CK5A/CK5BW030
CK5A/CK5BW036
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
CK3BA030
CK3BA036
CK5A/CK5BW030
CK5A/CK5BW036
29,000
29,000
29,000
29,000
NONE
NONE
NONE
NONE
10.50
10.50
10.50
10.50
—
—
—
—
10.50
10.50
10.50
10.50
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5AA030
CK3BA030
29,000
29,000
29,000
29,000
29,000
NONE
NONE
NONE
NONE
NONE
11.00
10.50
11.00
10.50
11.00
—
—
—
—
—
11.00
10.50
11.00
10.50
11.00
CK3BA036
CK5A/CK5BW030
CK5A/CK5BW036
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CK3BA030
CK3BA036
CK5A/CK5BW036
29,000
29,000
29,000
NONE
NONE
NONE
10.50
11.00
11.00
—
—
—
10.50
11.00
11.00
See notes on page 14.
—9—
COMBINATION RATINGS Continued
FACTORY-
BRYANT GAS
FURNACE OR
ACCESSORY
TDR†
TOT.
CAP.
BTUH
SUPPLIED
ENHANCE-
MENT
UNIT
SIZE-SERIES
INDOOR
MODEL
STANDARD
RATING
ACCESSORY
TXV‡
CC5A/CD5AA036*
CC5A/CD5AA042
CC5A/CD5AW042
CD5AW036
34,600
34,600
34,600
34,600
34,400
34,600
34,600
34,600
34,600
34,600
34,600
32,000
33,600
34,600
34,000
34,800
34,000
34,800
34,000
34,600
34,600
34,800
35,400
35,400
NONE
NONE
10.00
10.00
10.00
10.00
10.00
10.10
10.10
10.00
10.00
10.00
10.00
10.00
10.00
10.00
10.00
10.20
10.00
10.20
10.00
10.20
10.20
10.50
11.00
11.50
10.20
10.20
10.20
10.20
10.20
10.50
10.50
10.20
10.20
10.20
10.20
10.20
10.20
10.20
—
10.20
10.20
10.20
10.20
10.20
10.50
10.50
10.20
10.20
10.20
10.20
10.20
10.20
10.20
10.00
10.20
—
NONE
NONE
CE3AA036
NONE
CE3AA042
NONE
CF5AA036
NONE
CK3BA036
NONE
CK3BA042
NONE
CK5A/CK5BA036
CK5A/CK5BA042
CK5A/CK5BN036
CK5A/CK5BN042
CK5A/CK5BW036
F(A,B)4(A,B)NF036
F(A,B)4(A,B)N(F,B)042
FC4(B,C)NF036
FC4(B,C)N(F,B)042
FG3AAA036
NONE
NONE
NONE
NONE
NONE
TDR
TDR
—
TDR & TXV
TDR & TXV
NONE
—
—
—
10.20
—
10.20
—
FK4(C,D)NF001
FK4(C,D)NF002
FK4(C,D)NF003
FK4(C,D)NF005
FK4(C,D)NB006
TDR & TXV
TDR & TXV
TDR & TXV
TDR & TXV
TDR & TXV
—
—
—
—
—
—
—
—
COILS + 315(A,J)AV036070 VARIABLE-SPEED FURNACE
CC5A/CD5AA036
CE3AA036
33,000
32,600
33,000
33,000
33,000
33,000
33,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
10.5
11
11
10.5
11
9.7
9.6
9.8
9.7
9.7
9.8
9.7
CE3AA042
CK3BA036
11
11
CK5A/CK5BA036
CK5A/CK5BE042
CK5A/CK5BT036
11
11
11
11
11
11
COILS + 315(A,J)AV048090 VARIABLE-SPEED FURNACE
CC5A/CD5AA036
CC5A/CD5AA042
CC5A/CD5AW036
CE3AA036
33,000
33,000
33,000
32,600
33,000
33,000
33,000
33,000
33,000
33,000
33,000
33,000
33,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
10.5
11
11
11
11
11
11
11
11
11
11
11
11
10.5
11
11
11
11
11
11
11
11
11
9.85
9.95
9.85
9.75
9.95
9.85
9.9
CE3AA042
CK3BA036
CK3BA042
036-C, D
CK5A/CK5BA036
CK5A/CK5BA042
CK5A/CK5BE042
CK5A/CK5BT036
CK5A/CK5BT042
CK5A/CK5BW036
9.85
9.9
9.95
9.85
9.9
9.85
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CC5A/CD5AA036
CC5A/CD5AA042
CC5A/CD5AW036
CC5A/CD5AW042
CE3AA036
33,000
33,000
33,000
33,000
32,600
33,000
33,000
33,000
33,000
33,000
33,000
33,000
33,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
10.5
11
11
11
11
11
11
11
11
11
11
11
11
10.5
11
11
11
11
11
11
11
11
9.9
10.05
9.9
10
9.85
10
CE3AA042
CK3BA036
CK3BA042
CK5A/CK5BA036
CK5A/CK5BA042
CK5A/CK5BT036
CK5A/CK5BT042
CK5A/CK5BW036
9.95
10
9.95
10
9.95
10
9.95
COILS + 315(A,J)AV066135 VARIABLE-SPEED FURNACE
CC5A/CD5AA042
CC5A/CD5AW036
CC5A/CD5AW042
CE3AA036
33,000
33,000
33,000
32,600
33,000
33,000
33,000
33,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
10
9.85
9.95
9.8
11
11
10.5
11
10.5
11
CE3AA042
9.95
9.95
9.95
9.9
CK3BA042
CK5A/CK5BA042
CK5A/CK5BW036
11
11
11
11
11
11
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
CC5A/CD5AA042
CC5A/CD5AW036
CC5A/CD5AW042
CE3AA036
33,000
33,000
33,000
32,600
33,000
33,000
33,000
33,000
33,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
10.05
9.9
11
11
10
10.5
11
10.5
11
9.8
CE3AA042
10.05
10
CK3BA042
11
11
CK5A/CK5BA042
CK5A/CK5BT042
CK5A/CK5BW036
11
11
10
11
11
10
11
11
9.95
See notes on page 14.
—10—
COMBINATION RATINGS Continued
FACTORY-
BRYANT GAS
FURNACE OR
ACCESSORY
TDR†
TOT.
CAP.
BTUH
SUPPLIED
ENHANCE-
MENT
UNIT
SIZE-SERIES
INDOOR
MODEL
STANDARD
RATING
ACCESSORY
TXV‡
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5AA036
CK3BA036
34,600
34,000
34,000
34,000
34,000
NONE
NONE
NONE
NONE
NONE
11.00
10.50
10.50
10.50
10.50
—
—
—
—
—
11.00
10.50
10.50
10.50
10.50
CK3BA042
CK5A/CK5BA042
CK5A/CK5BW036
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5AA036
CK3BA036
34,600
34,000
34,000
34,000
33,000
NONE
NONE
NONE
NONE
NONE
11.00
10.50
10.50
10.50
10.50
—
—
—
—
—
11.00
10.50
10.50
10.50
10.50
CK3BA042
CK5A/CK5BA036
CK5A/CK5BN042
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5AA036
CK3BA036
34,600
34,000
34,000
34,000
34,000
NONE
NONE
NONE
NONE
NONE
11.00
10.50
10.50
10.50
10.50
—
—
—
—
—
11.00
10.50
10.50
10.50
10.50
CK3BA042
CK5A/CK5BA042
CK5A/CK5BW036
036-C, D
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
CK3BA036
CK3BA042
CK5A/CK5BA042
CK5A/CK5BW036
34,000
34,000
34,000
34,000
NONE
NONE
NONE
NONE
10.50
10.50
10.50
10.50
—
—
—
—
10.50
10.50
10.50
10.50
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5AA036
CK3BA036
34,600
34,000
34,000
34,000
34,000
NONE
NONE
NONE
NONE
NONE
11.00
10.50
10.50
10.50
10.50
—
—
—
—
—
11.00
10.50
10.50
10.50
10.50
CK3BA042
CK5A/CK5BA042
CK5A/CK5BW036
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CK3BA036
CK3BA042
CK5A/CK5BA042
CK5A/CK5BW036
34,000
34,000
34,000
34,000
NONE
NONE
NONE
NONE
10.50
10.50
10.50
10.50
—
—
—
—
10.50
10.50
10.50
10.50
CC5A/CD5AA042*
CC5A/CD5AC048
CC5A/CD5AW042
CC5A/CD5AW048
CD5AA048
39,500
39,000
39,500
40,000
40,000
39,500
39,500
40,000
39,500
40,000
39,500
40,000
38,500
39,000
40,000
39,500
40,500
39,500
40,500
40,000
41,500
40,000
41,000
NONE
NONE
10.00
10.00
10.00
10.10
10.10
10.00
10.10
10.10
10.00
10.10
10.00
10.10
10.00
10.10
10.10
10.00
10.50
10.00
10.50
10.10
11.50
11.00
11.20
10.20
10.50
10.20
10.50
10.50
10.20
10.50
10.50
10.20
10.50
10.20
10.50
10.20
10.50
10.50
—
10.20
10.50
10.20
10.50
10.50
10.20
10.50
10.50
10.20
10.50
10.20
10.50
10.20
10.50
10.50
10.00
10.50
—
NONE
NONE
NONE
CE3AA042
NONE
CE3AA048
NONE
CF5AA048
NONE
CK3BA042
NONE
CK3BA048
NONE
CK5A/CK5BA042
CK5A/CK5BA048
CK5A/CK5BN042
CK5A/CK5BN048
CK5A/CK5BW048
F(A,B)4(A,B)N(F,B)042
F(A,B)4(A,B)N(F,B)048
FC4(B,C)N(F,B)042
FC4(B,C)N(F,B)048
FG3AAA048
NONE
NONE
NONE
NONE
NONE
TDR
TDR
—
TDR & TXV
TDR & TXV
NONE
—
—
—
10.50
—
10.50
—
—
—
FK4(C,D)NB006
FK4(C,D)NF003
FK4(C,D)NF005
TDR & TXV
TDR & TXV
TDR & TXV
—
—
042-C, D
COILS + 315(A,J)AV048090 VARIABLE-SPEED FURNACE
CC5A/CD5AA042
CC5A/CD5AC048
CD5AA048
39,500
39,000
40,000
39,500
40,000
39,500
40,000
39,500
40,000
39,500
39,500
40,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
10.05
10.05
10.15
10.1
CE3AA042
CE3AA048
10.1
CK3BA042
10.05
10.15
10.05
10.15
10.1
10.05
10.15
CK3BA048
CK5A/CK5BA042
CK5A/CK5BA048
CK5A/CK5BE042
CK5A/CK5BT042
CK5A/CK5BT048
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CC5A/CD5AA042
CC5A/CD5AC048
CC5A/CD5AW042
CC5A/CD5AW048
CD5AA048
39,500
39,000
39,500
40,000
40,000
39,500
40,000
39,500
40,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
10.1
10.15
10.05
10.25
10.25
10.2
CE3AA042
CE3AA048
10.2
CK3BA042
10.15
10.25
CK3BA048
See notes on page 14.
—11—
COMBINATION RATINGS Continued
FACTORY-
BRYANT GAS
FURNACE OR
ACCESSORY
TDR†
TOT.
CAP.
BTUH
SUPPLIED
ENHANCE-
MENT
UNIT
SIZE-SERIES
INDOOR
MODEL
STANDARD
RATING
ACCESSORY
TXV‡
CK5A/CK5BA042
CK5A/CK5BA048
CK5A/CK5BT042
CK5A/CK5BT048
CK5A/CK5BW048
39,500
40,000
39,500
40,000
40,000
TDR
TDR
TDR
TDR
TDR
11
11
11
11
11
11
11
11
11
11
10.15
10.25
10.15
10.25
10.25
COILS + 315(A,J)AV066135 VARIABLE-SPEED FURNACE
CC5A/CD5AA042
CC5A/CD5AC048
CC5A/CD5AW042
CC5A/CD5AW048
CD5AA048
39,500
39,000
39,500
40,000
40,000
39,500
40,000
39,500
40,000
39,500
40,000
39,500
40,000
40,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
10.15
10.15
10.05
10.25
10.3
CE3AA042
10.2
CE3AA048
10.2
CK3BA042
10.15
10.25
10.15
10.25
10.15
10.25
10.25
CK3BA048
CK5A/CK5BA042
CK5A/CK5BA048
CK5A/CK5BT042
CK5A/CK5BT048
CK5A/CK5BW048
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
CC5A/CD5AA042
CC5A/CD5AC048
CC5A/CD5AW042
CC5A/CD5AW048
CD5AA048
39,500
39,000
39,500
40,000
40,000
39,500
40,000
39,500
40,000
39,500
40,000
39,500
40,000
40,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
10.15
10.2
10.1
10.3
10.3
CE3AA042
10.2
CE3AA048
10.25
10.15
10.3
CK3BA042
CK3BA048
CK5A/CK5BA042
CK5A/CK5BA048
CK5A/CK5BT042
CK5A/CK5BT048
CK5A/CK5BW048
10.15
10.3
042-C, D
10.15
10.3
10.3
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CK3BA042
CK5A/CK5BN042
39,500
38,500
NONE
NONE
10.50
10.50
—
—
10.50
10.50
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5AA042
CK3BA042
40,000
39,500
39,500
39,500
39,500
NONE
NONE
NONE
NONE
NONE
11.00
10.50
10.50
10.50
10.50
—
—
—
—
—
11.00
10.50
10.50
10.50
10.50
CK3BA048
CK5A/CK5BA042
CK5A/CK5BA048
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
CK3BA042
CK3BA048
CK5A/CK5BA042
CK5A/CK5BA048
39,500
39,500
39,500
39,500
NONE
NONE
NONE
NONE
10.50
10.50
10.50
10.50
—
—
—
—
10.50
10.50
10.50
10.50
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5AA042
CK3BA042
40,000
39,500
39,500
39,500
39,500
NONE
NONE
NONE
NONE
NONE
11.00
10.50
11.00
10.50
11.00
—
—
—
—
—
11.00
10.50
11.00
10.50
11.00
CK3BA048
CK5A/CK5BA042
CK5A/CK5BA048
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CK3BA042
CK3BA048
CK5A/CK5BA042
CK5A/CK5BW048
39,500
39,500
39,500
39,500
NONE
NONE
NONE
NONE
10.50
11.00
10.50
11.00
—
—
—
—
10.50
11.00
10.50
11.00
CD5AA048*
CC5A/CD5AA060
CC5A/CD5AC048
CC5A/CD5AW048
CC5A/CD5AW060
CE3AA048
46,000
46,000
45,000
46,000
47,500
46,500
48,000
46,000
46,000
46,000
44,500
46,000
46,000
47,500
46,000
46,000
46,500
48,000
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
TDR
10.20
10.20
10.00
10.20
10.50
10.20
10.30
10.30
10.20
10.20
10.20
10.20
10.20
10.50
10.20
10.20
10.50
10.50
10.50
10.50
10.20
10.50
11.00
10.50
10.50
10.50
10.50
10.50
10.50
10.50
10.50
11.00
10.50
10.50
—
10.50
10.50
10.20
10.50
11.00
10.50
10.50
10.50
10.50
10.50
10.50
10.50
10.50
11.00
10.50
10.50
10.50
10.50
CE3AA060
CF5AA048
CK5A/CK5BA048
CK5A/CK5BA060
CK5A/CK5BN048
CK5A/CK5BN060
CK5A/CK5BW048
CK5A/CK5BX060
CK3BA048
048-C
CK3BA060
F(A,B)4(A,B)N(F,B)048
F(A,B)4(A,B)N(F,B)060
TDR
—
See notes on page 14.
—12—
COMBINATION RATINGS Continued
FACTORY-
BRYANT GAS
FURNACE OR
ACCESSORY
TDR†
TOT.
CAP.
BTUH
SUPPLIED
ENHANCE-
MENT
UNIT
SIZE-SERIES
INDOOR
MODEL
STANDARD
RATING
ACCESSORY
TXV‡
FB4(A,B)NB070
FC4(B,C)N(F,B)048
FC4(B,C)N(F,B)060
FC4(B,C)NB054
FC4(B,C)NB070
FG3AAA048
48,000
46,500
47,500
48,000
48,000
46,000
47,500
48,000
47,500
TDR
11.00
10.40
10.50
11.00
11.00
10.00
10.30
11.50
11.00
—
—
11.00
—
TDR & TXV
TDR & TXV
TDR & TXV
TDR & TXV
NONE
—
—
—
—
—
—
10.50
10.50
—
10.50
10.50
—
FG3AAA060
NONE
TDR & TXV
TDR & TXV
FK4(C,D)NB006
FK4(C,D)NF005
—
—
COILS + 315(A,J)AV048090 VARIABLE-SPEED FURNACE
CC5A/CD5AC048
CD5AA048
45,500
45,500
45,500
46,500
45,500
45,500
45,500
TDR
TDR
TDR
TDR
TDR
TDR
TDR
10.5
10.5
10.5
11
10.5
10.5
10.5
10.5
10.5
10.5
11
10.5
10.5
10.5
9.5
9.55
9.55
9.85
9.6
CE3AA048
CE3AA060
CK3BA048
CK5A/CK5BA048
CK5A/CK5BT048
9.6
9.6
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AC048
CC5A/CD5AW048
CD5AA048
46,000
45,500
45,500
45,500
45,500
46,500
45,500
46,500
45,500
46,500
45,500
46,500
45,500
47,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
10.5
10.5
10.5
10.5
11
11
10.5
10.5
10.5
10.5
11
9.75
9.65
9.7
9.7
CE3AA048
9.75
10
CE3AA060
CK3BA048
10.5
11
10.5
11
9.75
9.95
9.75
9.95
9.75
9.95
9.75
10.2
CK3BA060
CK5A/CK5BA048
CK5A/CK5BA060
CK5A/CK5BT048
CK5A/CK5BT060
CK5A/CK5BW048
CK5A/CK5BX060
10.5
11
10.5
11
10.5
11
10.5
11
10.5
10.5
11
11
COILS + 315(A,J)AV066135 VARIABLE-SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AC048
CC5A/CD5AW048
CC5A/CD5AW060
CD5AA048
46,000
45,500
45,500
46,500
45,500
45,500
46,500
45,500
46,500
45,500
46,500
45,500
46,500
45,500
47,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
10.5
10.5
11
11
10.5
10.5
11
9.75
9.6
9.7
10
10.5
10.5
11
10.5
10.5
11
9.7
CE3AA048
9.7
CE3AA060
10
CK3BA048
10.5
11
10.5
11
9.7
CK3BA060
9.95
9.7
CK5A/CK5BA048
CK5A/CK5BA060
CK5A/CK5BT048
CK5A/CK5BT060
CK5A/CK5BW048
CK5A/CK5BX060
10.5
11
10.5
11
048-C
9.95
9.7
10.5
11
10.5
11
9.95
9.7
10.5
10.5
11
11
10.15
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AC048
CC5A/CD5AW048
CC5A/CD5AW060
CD5AA048
46,000
45,500
45,500
46,500
45,500
45,500
46,500
45,500
46,500
45,500
46,500
45,500
46,500
45,500
47,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11
11
11
11
9.8
9.7
11
11
9.75
10.05
9.75
9.75
10.05
9.75
10
11
11
11
11
CE3AA048
10.5
11
10.5
11
CE3AA060
CK3BA048
10.5
11
10.5
11
CK3BA060
CK5A/CK5BA048
CK5A/CK5BA060
CK5A/CK5BT048
CK5A/CK5BT060
CK5A/CK5BW048
CK5A/CK5BX060
10.5
11
10.5
11
9.75
10
10.5
11
10.5
11
9.75
10
10.5
10.5
11
9.75
10.2
11
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CK3BA048
CK3BA060
CK5A/CK5BA048
45,000
45,500
45,000
NONE
NONE
NONE
10.50
10.50
10.50
—
—
—
10.50
10.50
10.50
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
CK3BA060
45,500
45,500
45,500
47,000
NONE
NONE
NONE
NONE
10.50
10.50
10.50
11.00
—
—
—
—
10.50
10.50
10.50
11.00
CK5A/CK5BA060
CK5A/CK5BN060
CK5A/CK5BX060
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5AW060
CK3BA048
46,500
45,000
45,500
45,000
45,500
47,000
NONE
NONE
NONE
NONE
NONE
NONE
11.00
10.50
11.00
10.50
11.00
11.00
—
—
—
—
—
—
11.00
10.50
11.00
10.50
11.00
11.00
CK3BA060
CK5A/CK5BA048
CK5A/CK5BA060
CK5A/CK5BX060
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CK3BA048
CK3BA060
CK5A/CK5BA060
CK5A/CK5BW048
CK5A/CK5BX060
45,000
45,500
45,500
45,000
47,000
NONE
NONE
NONE
NONE
NONE
10.50
11.00
11.00
10.50
11.00
—
—
—
—
—
10.50
11.00
11.00
10.50
11.00
See notes on page 14.
—13—
COMBINATION RATINGS Continued
FACTORY-
BRYANT GAS
FURNACE OR
ACCESSORY
TDR†
TOT.
CAP.
BTUH
SUPPLIED
ENHANCE-
MENT
UNIT
SIZE-SERIES
INDOOR
MODEL
STANDARD
RATING
ACCESSORY
TXV‡
CC5A/CD5AW060*
CC5A/CD5AA060
CE3AA060
57,000
54,500
57,500
54,500
54,500
54,500
57,000
57,500
58,500
58,500
57,500
56,500
58,000
NONE
NONE
10.20
10.00
10.20
10.00
10.00
10.00
10.20
10.00
10.50
10.50
10.00
10.20
11.00
10.50
10.20
10.50
10.20
10.20
10.20
10.50
—
10.50
10.20
10.50
10.20
10.20
10.20
10.50
10.00
10.50
—
NONE
CK3BA060
NONE
CK5A/CK5BA060
CK5A/CK5BN060
CK5A/CK5BX060
F(A,B)4(A,B)N(F,B)060
FB4(A,B)NB070
FC4(B,C)NB070
FC4(B,C)N(F,B)060
FG3AAA060
NONE
NONE
NONE
TDR
TDR
—
TDR & TXV
TDR & TXV
NONE
—
—
10.50
—
—
10.50
—
FK4(C,D)NB006
TDR & TXV
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CC5A/CD5AA060
CE3AA060
55,000
56,500
56,000
56,000
56,000
56,500
TDR
TDR
TDR
TDR
TDR
TDR
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
9
9.3
CK3BA060
9.15
9.15
9.15
9.4
CK5A/CK5BA060
CK5A/CK5BT060
CK5A/CK5BX060
060-C
COILS + 315(A,J)AV066135 VARIABLE-SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AW060
CE3AA060
55,000
56,000
56,500
56,000
56,000
56,000
56,500
TDR
TDR
TDR
TDR
TDR
TDR
TDR
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
9
9.25
9.3
CK3BA060
9.15
9.15
9.15
9.4
CK5A/CK5BA060
CK5A/CK5BT060
CK5A/CK5BX060
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AW060
CE3AA060
55,000
56,000
56,500
56,000
56,000
56,000
56,500
TDR
TDR
TDR
TDR
TDR
TDR
TDR
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
9.1
9.3
9.35
9.2
CK3BA060
CK5A/CK5BA060
CK5A/CK5BT060
CK5A/CK5BX060
9.2
9.2
9.45
*
Tested combination.
†
In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use
either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. Most Bryant furnaces are equipped with TDR.
Based on computer simulation, TXV must be hard shutoff type.
‡
NOTES: 1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.
2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other com-
binations are determined under DOE computer simulation procedures.
3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.
—14—
DETAILED COOLING CAPACITIES*
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
MBtuh†
115
Capacity
MBtuh†
125
Capacity
Total
Total
System
Total
System
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
System
System
CFM
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C018-C, D Outdoor Section With CC5A/CD5AA018 Indoor Section
72
67
62
57
72
67
62
57
72
67
62
57
19.7
17.9
16.1
15.0
20.1
18.3
16.5
15.7
20.5
18.6
16.8
16.2
9.50
11.8
14.0
15.0
9.89
12.5
14.9
15.7
10.3
13.1
15.8
16.2
1.69
1.65
1.60
1.58
1.73
1.68
1.64
1.62
1.76
1.72
1.68
1.67
18.6
16.8
15.1
14.3
19.0
17.2
15.5
14.9
19.3
17.5
15.8
15.4
9.09
11.4
13.6
14.3
9.47
12.0
14.4
14.9
9.83
12.6
15.2
15.4
1.80
1.75
1.70
1.68
1.84
1.79
1.74
1.72
1.88
1.83
1.78
1.77
17.5
15.8
14.1
13.5
17.8
16.1
14.4
14.1
18.1
16.3
14.7
14.6
8.66
10.9
13.0
13.5
9.03
11.6
13.8
14.1
9.39
12.2
14.5
14.6
1.91
1.85
1.79
1.77
1.95
1.89
1.83
1.82
1.99
1.93
1.87
1.87
16.3
14.7
13.1
12.8
16.6
15.0
13.4
13.3
16.9
15.2
13.7
13.7
8.23
10.5
12.5
12.8
8.60
11.1
13.2
13.3
8.95
11.7
13.7
13.7
2.01
1.94
1.88
1.86
2.06
1.99
1.92
1.91
2.09
2.03
1.97
1.97
15.2
13.6
12.1
12.0
15.4
13.8
12.4
12.5
15.6
14.0
12.7
12.9
7.80
10.0
12.0
12.0
8.17
10.6
12.4
12.5
8.51
11.2
12.7
12.9
2.12
2.04
1.96
1.95
2.16
2.08
2.01
2.01
2.20
2.13
2.06
2.06
525
600
675
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Section
Unit
Indoor
Section
Unit
Size
Size
018
024
024
024
024
024
018
024
024
018
024
024
018
024
024
001
002
—
Capacity
1.00
1.03
1.03
1.05
1.05
1.03
1.00
1.03
1.03
0.99
1.05
1.05
0.99
1.05
1.02
1.05
1.05
—
Power
1.00
1.01
1.01
1.01
1.01
1.01
1.01
1.01
1.01
1.00
1.02
1.02
1.00
1.02
1.01
0.94
0.94
—
Capacity
Power
CC5A/CD5AA
COILS + 315(A,J)AV036070 VARIABLE-SPEED FURNACE
CC5A/CD5AA
018
024
024
024
024
018
024
024
1.00
1.02
1.02
1.02
1.02
1.00
1.02
1.02
0.91
0.91
0.91
0.91
0.89
0.89
0.89
0.89
CC5A/CD5AA
CE3AA
CF5AA
CK3BA
CK5A/CK5BA
CC5A/CD5AW
CE3AA
CK3BA
CK5A/CK5BA
CK5A/CK5BW
F(A,B)4(A,B)NF
CK5A/CK5BW
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5AA 018 1.02 0.93
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
FC4(B,C)NF
FF1DNA
CC5A/CD5AA
CK5A/CK5BW
CK3BA
018
024
024
1.02
1.02
1.02
0.93
0.94
0.94
FG3AA
FK4(C,D)NF
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CK3BA
CK5A/CK5BW
018
024
024
1.02
1.02
1.02
0.93
0.94
0.94
—
—
—
See notes on page 24.
—15—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
MBtuh†
115
Capacity
MBtuh†
125
Capacity
Total
Total
System
Total
System
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
System
System
CFM
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C024-C, D Outdoor Section With CC5A/CD5AA024 Indoor Section
72
67
62
57
72
67
62
57
72
67
62
57
26.3
24.0
21.7
20.5
26.8
24.5
22.2
21.4
27.4
25.1
23.0
22.7
12.9
16.2
19.3
20.5
13.4
17.1
20.6
21.4
14.4
18.9
22.7
22.7
2.34
2.27
2.20
2.17
2.40
2.33
2.26
2.23
2.50
2.43
2.37
2.36
24.8
22.6
20.4
19.5
25.3
23.0
20.9
20.3
25.9
23.6
21.7
21.6
12.3
15.6
18.7
19.5
12.9
16.5
19.9
20.3
13.9
18.3
21.6
21.6
2.49
2.40
2.32
2.28
2.54
2.46
2.38
2.36
2.65
2.57
2.50
2.49
23.3
21.2
19.1
18.5
23.8
21.6
19.5
19.3
24.3
22.1
20.4
20.4
11.8
15.0
18.0
18.5
12.3
15.9
19.1
19.3
13.3
17.7
20.4
20.4
2.62
2.53
2.43
2.41
2.68
2.59
2.49
2.48
2.79
2.70
2.63
2.62
21.8
19.8
17.8
17.5
22.2
20.1
18.2
18.2
22.7
20.5
19.2
19.2
11.2
14.4
17.3
17.5
11.8
15.4
18.2
18.2
12.8
17.1
19.2
19.2
2.75
2.65
2.54
2.53
2.82
2.71
2.61
2.61
2.93
2.81
2.75
2.75
20.3
18.3
16.5
16.5
20.6
18.6
17.1
17.1
21.0
18.9
18.0
18.0
10.7
13.8
16.5
16.5
11.2
14.8
17.1
17.1
12.2
16.4
18.0
18.0
2.88
2.77
2.66
2.65
2.94
2.82
2.73
2.73
3.06
2.93
2.88
2.88
700
800
900
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Unit
Indoor
Unit
Size
Section
Size
024
030
024
030
024
030
024
024
030
024
030
024
030
024
030
024
030
024
030
024
001
002
003
Capacity
1.00
1.00
1.00
1.00
1.01
1.02
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.01
1.00
1.02
1.00
1.02
0.97
1.04
1.04
1.04
Power
1.00
1.00
1.00
1.00
1.00
1.01
1.00
1.00
1.01
1.00
1.01
1.00
1.01
1.00
1.00
1.00
1.00
1.01
1.02
1.00
0.95
0.95
0.93
Section
Capacity
0.99
1.00
0.99
1.00
0.99
1.00
0.99
1.00
Power
CC5A/CD5AA
CC5A/CD5AW
CE3AA
CC5A/CD5AW
024
030
024
030
024
030
024
030
024
030
0.91
0.90
0.91
0.90
0.90
0.90
0.90
0.90
0.90
0.90
CE3AA
CK3BA
CF5AA
CK3BA
CK5A/CK5BA
CK5A/CK5BW
0.99
1.00
CK5A/CK5BA
CK5A/CK5BW
F(A,B)4(A,B)NF
FC4(B,C)NF
FF1DNA
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CK3BA
024
024
030
030
0.98
0.98
1.01
1.01
0.93
0.95
0.95
0.95
CK5A/CK5BW
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CK3BA
024
024
030
024
030
0.98
0.98
1.01
0.98
1.01
0.93
0.95
0.95
0.95
0.95
FG3AAA
FK4(C,D)NF
CK5A/CK5BW
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CK3BA
024
024
030
024
030
0.98
0.98
1.01
0.98
1.01
0.93
0.93
0.94
0.93
0.94
COILS + 315(A,J)AV036070 VARIABLE-SPEED FURNACE
CC5A/CD5AA
024
030
—
0.99
1.00
—
0.91
0.90
—
CK5A/CK5BW
See notes on page 24.
—16—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
MBtuh†
115
Capacity
MBtuh†
125
Capacity
Total
Total
System
Total
System
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
System
System
CFM
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C030-C, D Outdoor Section With CC5A/CD5AA030 Indoor Section
72
67
62
57
32.6
29.7
26.9
25.4
15.9
20.0
23.9
25.4
2.90
2.83
2.74
2.69
30.8
28.1
25.3
24.2
15.2
19.3
23.1
24.2
3.11
3.01
2.90
2.86
29.0
26.4
23.7
23.0
14.6
18.5
22.3
23.0
3.30
3.19
3.07
3.03
27.2
24.6
22.2
21.8
13.9
17.8
21.4
21.8
3.49
3.35
3.22
3.20
25.3
22.9
20.7
20.5
13.2
17.2
20.5
20.5
3.67
3.52
3.37
3.37
875
1000
1125
72
67
62
57
33.2
30.4
27.5
26.5
16.6
21.2
25.4
26.5
2.97
2.89
2.81
2.77
31.4
28.6
25.9
25.2
15.9
20.4
24.6
25.2
3.18
3.08
2.98
2.95
29.5
26.8
24.3
23.9
15.2
19.7
23.6
23.9
3.37
3.26
3.14
3.13
27.6
25.0
22.7
22.6
14.5
19.0
22.6
22.6
3.57
3.43
3.30
3.30
25.6
23.3
21.3
21.3
13.8
18.3
21.3
21.3
3.74
3.60
3.47
3.47
72
67
62
57
33.7
30.8
28.0
27.4
17.2
22.3
26.8
27.4
3.03
2.95
2.87
2.85
31.8
29.0
26.3
26.0
16.5
21.5
25.8
26.0
3.24
3.15
3.04
3.03
29.8
27.2
24.7
24.7
15.8
20.8
24.7
24.7
3.44
3.33
3.21
3.21
27.8
25.3
23.3
23.3
15.1
20.1
23.3
23.3
3.63
3.50
3.39
3.39
25.9
23.5
21.9
21.9
14.4
19.3
21.9
21.9
3.82
3.67
3.56
3.57
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Section
CC5A/CD5AA
Unit
Indoor
Unit
Size
Size
030
036
030
036
030
036
036
030
036
030
036
036
030
036
030
036
030
036
030
036
001
002
003
005
Capacity
1.00
1.01
1.00
1.01
0.99
1.01
1.01
1.00
1.01
1.00
1.01
0.94
1.00
1.01
0.99
1.01
0.99
1.01
0.99
1.01
1.03
1.03
1.03
1.05
Power
1.00
1.01
1.00
1.01
1.00
1.01
1.01
1.00
1.01
1.00
1.01
1.01
1.00
1.01
1.00
1.02
1.00
1.02
1.01
1.00
0.97
0.97
0.97
0.94
Section
Capacity
1.00
1.02
1.00
1.04
1.00
1.04
1.00
1.04
Power
CE3AA
030
036
030
036
030
036
030
036
0.92
0.93
0.93
0.93
0.93
0.93
0.93
0.93
CK3BA
CC5A/CD5AW
CD5AW
CK5A/CK5BA
CK5A/CK5BW
CE3AA
CF5AA
CK3BA
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
0.95
0.97
0.97
0.97
0.97
CK5A/CK5BA
CC5A/CD5AA
CK3BA
030
030
036
030
036
1.01
1.01
1.01
1.01
1.01
CK5A/CK5BN
CK5A/CK5BW
CK5A/CK5BW
F(A,B)4(A,B)NF
FC4(B,C)NF
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
0.95
0.97
0.98
0.98
0.98
0.97
CC5A/CD5AA
CK3BA
030
030
036
036
036
030
1.01
1.01
1.01
1.01
0.94
1.01
FF1DNA
FG3AAA
FK4(C,D)NF
CK5A/CK5BA
CK5A/CK5BN
CK5A/CK5BW
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
0.95
0.97
0.97
0.97
0.97
CC5A/CD5AA
CK3BA
030
030
036
030
036
1.01
1.01
1.01
1.01
1.01
COILS + 315(A,J)AV036070 VARIABLE-SPEED FURNACE
CC5A/CD5AA
030
036
030
030
036
030
036
030
036
036
030
1.00
1.04
1.00
1.00
1.02
1.00
1.04
1.00
1.04
1.04
1.00
0.94
0.95
0.94
0.93
0.95
0.94
0.94
0.94
0.94
0.94
0.94
CK5A/CK5BW
CC5A/CD5AW
CE3AA
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
0.97
0.98
0.97
0.98
CK3BA
030
036
030
036
1.01
1.01
1.01
1.01
CK3BA
CK5A/CK5BW
CK5A/CK5BA
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
0.95
0.95
0.96
0.95
0.96
CC5A/CD5AA
CK3BA
030
030
036
030
036
1.01
1.01
1.01
1.01
1.01
CK5A/CK5BT
CK5A/CK5BW
COILS + 315(A,J)AV048090 VARIABLE-SPEED FURNACE
CK5A/CK5BW
CC5A/CD5AA
CC5A/CD5AW
030
036
030
036
—
1.00
1.04
1.00
1.04
—
0.93
0.93
0.93
0.93
—
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
0.95
0.96
0.96
CK3BA
030
036
036
1.01
1.01
1.01
CK5A/CK5BW
See notes on page 24.
—17—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
Total
Total
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
System
System
CFM
1050
1200
1350
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C036-C, D Outdoor Section With CC5A/CD5AA036 Indoor Section
72
67
62
57
72
67
62
57
72
67
62
57
39.6
36.0
32.7
31.3
19.6
24.9
29.8
31.3
3.42
3.32
3.23
3.19
3.49
3.40
3.31
3.29
3.56
3.47
3.38
3.38
37.4
34.0
30.7
29.8
38.1
34.6
31.4
31.1
38.5
35.0
32.1
32.1
18.8
24.0
28.9
29.8
3.65
3.54
3.43
3.39
35.2
31.9
28.8
28.3
18.0
23.2
27.8
28.3
3.88
3.75
3.62
3.59
32.9
29.8
27.0
26.8
17.2
22.3
26.7
26.8
4.08
3.94
3.79
3.79
4.17
4.03
3.90
3.90
4.25
4.11
4.00
4.00
30.5
27.7
25.3
25.3
16.4
21.5
25.3
25.3
4.28
4.12
3.98
3.98
40.3
36.7
33.4
32.6
20.5
26.4
31.8
32.6
19.7
25.5
30.7
31.1
3.73
3.62
3.51
3.50
35.8
32.4
29.5
29.5
18.9
24.7
29.4
29.5
3.96
3.83
3.71
3.71
33.3
30.3
27.8
27.8
18.1
23.9
27.8
27.8
31.0
28.1
26.2
26.2
17.3
23.0
26.2
26.2
4.38
4.21
4.10
4.10
40.8
37.2
34.0
33.7
21.4
27.9
33.5
33.7
20.6
27.0
32.1
32.1
3.80
3.69
3.59
3.59
36.1
32.8
30.4
30.4
19.7
26.1
30.4
30.4
4.03
3.91
3.80
3.80
33.6
30.6
28.6
28.6
18.9
25.3
28.6
28.6
31.4
28.3
26.9
26.9
18.1
24.3
26.9
26.9
4.47
4.29
4.20
4.21
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Unit
Indoor
Unit
Size
042
036
042
036
Section
Size
036
042
042
036
036
042
036
036
042
036
042
036
042
036
036
042
036
042
036
005
006
001
002
003
005
Capacity
1.00
1.00
1.00
1.00
0.99
1.00
1.00
1.00
1.00
1.00
1.00
0.92
0.97
1.00
0.98
1.01
0.98
1.01
0.98
1.02
1.02
1.00
1.00
1.01
1.02
Power
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.97
1.00
1.00
1.01
1.01
1.01
1.01
0.99
0.95
0.95
0.98
0.98
0.94
0.93
Section
Capacity
0.99
0.99
0.99
0.99
Power
CC5A/CD5AA
CK5A/CK5BE
CK5A/CK5BT
0.91
0.92
0.92
0.92
CC5A/CD5AW
CD5AW
CK5A/CK5BW
CE3AA
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AW
CE3AA
036
042
036
042
036
042
036
042
036
042
036
042
036
0.99
0.99
0.99
0.99
0.98
0.99
0.99
0.99
0.99
0.99
0.99
0.99
0.99
0.92
0.91
0.92
0.91
0.91
0.91
0.92
0.91
0.92
0.91
0.92
0.91
0.92
CF5AA
CK3BA
CK5A/CK5BA
CK5A/CK5BN
CK3BA
CK5A/CK5BW
F(A,B)4(A,B)NF
F(A,B)4(A,B)N(F,B)
FC4(B,C)NF
FC4(B,C)N(F,B)
FG3AAA
FK4(C,D)NB
CK5A/CK5BA
CK5A/CK5BT
CK5A/CK5BW
COILS + 315(A,J)AV066135 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AW
042
036
042
036
042
042
042
036
0.99
0.99
0.99
0.98
0.99
0.99
0.99
0.99
0.91
0.92
0.91
0.92
0.91
0.91
0.91
0.92
FK4(C,D)NF
CE3AA
CK3BA
CK5A/CK5BA
CK5A/CK5BW
COILS + 315(A,J)AV036070 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CE3AA
036
036
042
036
036
042
036
0.99
0.98
0.99
0.99
0.99
0.99
0.99
0.94
0.93
0.93
0.94
0.94
0.93
0.94
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AW
042
036
042
036
042
042
042
042
036
0.99
0.99
0.99
0.98
0.99
0.99
0.99
0.99
0.99
0.90
0.92
0.91
0.91
0.91
0.91
0.91
0.91
0.92
CK3BA
CK5A/CK5BA
CK5A/CK5BE
CK5A/CK5BT
CE3AA
COILS + 315(A,J)AV048090 VARIABLE-SPEED FURNACE
CK3BA
CC5A/CD5AA
036
042
036
036
042
036
042
036
042
0.99
0.99
0.99
0.98
0.99
0.99
0.99
0.99
0.99
0.92
0.91
0.92
0.92
0.92
0.92
0.92
0.92
0.92
CK5A/CK5BA
CK5A/CK5BT
CK5A/CK5BW
CC5A/CD5AW
CE3AA
COILS + 355MAV042040 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CK3BA
036
036
042
042
036
1.00
0.98
0.98
0.98
0.98
0.92
0.94
0.93
0.93
0.94
CK3BA
CK5A/CK5BA
CK5A/CK5BA
CK5A/CK5BW
See notes on page 24.
—18—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
MBtuh†
115
Capacity
MBtuh†
125
Capacity
Total
Total
System
Total
System
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
System
System
CFM
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C036-C, D Outdoor Section With CC5A/CD5AA036 Indoor Section Continued
72
67
62
57
72
67
62
57
72
67
62
57
39.6
36.0
32.7
31.3
40.3
36.7
33.4
32.6
40.8
37.2
34.0
33.7
19.6
24.9
29.8
31.3
20.5
26.4
31.8
32.6
21.4
27.9
33.5
33.7
3.42
3.32
3.23
3.19
3.49
3.40
3.31
3.29
3.56
3.47
3.38
3.38
37.4
34.0
30.7
29.8
38.1
34.6
31.4
31.1
38.5
35.0
32.1
32.1
18.8
24.0
28.9
29.8
19.7
25.5
30.7
31.1
20.6
27.0
32.1
32.1
3.65
3.54
3.43
3.39
3.73
3.62
3.51
3.50
3.80
3.69
3.59
3.59
35.2
31.9
28.8
28.3
35.8
32.4
29.5
29.5
36.1
32.8
30.4
30.4
18.0
23.2
27.8
28.3
18.9
24.7
29.4
29.5
19.7
26.1
30.4
30.4
3.88
3.75
3.62
3.59
3.96
3.83
3.71
3.71
4.03
3.91
3.80
3.80
32.9
29.8
27.0
26.8
33.3
30.3
27.8
27.8
33.6
30.6
28.6
28.6
17.2
22.3
26.7
26.8
18.1
23.9
27.8
27.8
18.9
25.3
28.6
28.6
4.08
3.94
3.79
3.79
4.17
4.03
3.90
3.90
4.25
4.11
4.00
4.00
30.5
27.7
25.3
25.3
31.0
28.1
26.2
26.2
31.4
28.3
26.9
26.9
16.4
21.5
25.3
25.3
17.3
23.0
26.2
26.2
18.1
24.3
26.9
26.9
4.28
4.12
3.98
3.98
4.38
4.21
4.10
4.10
4.47
4.29
4.20
4.21
1050
1200
1350
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Unit
Size
Indoor
Unit
Size
042
036
Section
Capacity
Power
Section
Capacity
0.98
0.98
Power
0.94
0.94
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CK5A/CK5BA
CK5A/CK5BW
CC5A/CD5AA
036
036
042
036
042
1.00
0.98
0.98
0.98
0.95
0.92
0.94
0.94
0.94
0.94
CK3BA
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CK3BA
036
036
042
042
036
1.00
0.98
0.98
0.98
0.98
0.92
0.92
0.92
0.92
0.92
CK5A/CK5BA
CK5A/CK5BN
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CK5A/CK5BA
CK5A/CK5BW
CC5A/CD5AA
CK3BA
036
036
042
042
036
1.00
0.98
0.98
0.98
0.98
0.92
0.93
0.93
0.93
0.93
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CK3BA
036
042
042
036
—
0.98
0.98
0.98
0.98
—
0.93
0.92
0.92
0.93
—
CK5A/CK5BA
CK5A/CK5BW
CK5A/CK5BA
CK5A/CK5BW
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
CK3BA
036
042
0.98
0.98
0.94
0.94
See notes on page 24.
—19—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
Total
Total
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
System
System
CFM
1225
1400
1575
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C042-C, D Outdoor Section With CC5A/CD5AA042 Indoor Section
72
67
62
57
72
67
62
57
72
67
62
57
45.2
41.2
37.4
35.9
22.4
28.3
34.0
35.9
4.01
3.89
3.77
3.72
4.10
3.98
3.86
3.83
4.19
4.06
3.95
3.94
42.6
38.8
35.3
34.2
43.3
39.5
36.1
35.5
43.8
40.0
36.7
36.6
21.4
27.4
32.9
34.2
4.25
4.11
3.97
3.93
40.1
36.6
33.2
32.5
20.5
26.4
31.8
32.5
4.48
4.33
4.18
4.15
37.6
34.3
31.1
30.8
19.6
25.5
30.6
30.8
4.72
4.55
4.39
4.38
4.82
4.65
4.51
4.51
4.90
4.74
4.63
4.63
35.1
32.0
29.1
29.1
18.7
24.6
29.1
29.1
4.95
4.77
4.60
4.59
46.0
42.0
38.2
37.3
23.4
30.1
36.2
37.3
22.4
29.1
35.0
35.5
4.34
4.20
4.08
4.05
40.6
37.1
34.0
33.7
21.4
28.1
33.7
33.7
4.57
4.43
4.30
4.28
38.1
34.8
31.9
31.9
20.6
27.2
31.9
31.9
35.5
32.4
30.1
30.1
19.7
26.3
30.1
30.1
5.05
4.87
4.74
4.73
46.5
42.5
38.9
38.5
24.3
31.7
38.1
38.5
23.3
30.7
36.6
36.6
4.43
4.29
4.17
4.16
41.2
37.5
34.8
34.7
22.4
29.7
34.8
34.7
4.67
4.52
4.40
4.40
38.4
35.1
32.8
32.8
21.4
28.8
32.8
32.8
35.8
32.6
30.9
30.9
20.6
27.8
30.9
30.9
5.14
4.96
4.86
4.85
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Unit
Indoor
Unit
Size
Section
Size
042
048
042
048
042
048
048
042
048
042
048
042
048
048
042
048
042
048
048
003
005
006
Capacity
1.00
0.99
1.00
1.01
1.00
1.00
1.01
1.00
1.01
1.00
1.01
0.97
0.99
1.01
1.00
1.03
1.00
1.03
0.10
1.01
1.04
1.05
Power
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.01
1.02
1.01
1.02
1.00
0.92
0.95
0.94
Section
Capacity
1.00
0.99
1.00
0.99
1.00
0.99
1.00
0.99
Power
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
CD5AA
CE3AA
048
042
048
042
048
042
048
042
048
048
0.93
0.92
0.93
0.93
0.93
0.92
0.93
0.93
0.93
0.93
CK3BA
CE3AA
CK5A/CK5BA
CK5A/CK5BT
CK5A/CK5BW
CF5AA
CK3BA
1.00
1.00
CK5A/CK5BA
CK5A/CK5BN
CK5A/CK5BW
COILS + 315(A,J)AV066135 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
042
048
042
048
048
042
048
042
048
042
048
042
048
048
0.99
0.98
0.99
1.00
1.00
0.99
1.00
0.99
1.00
0.99
1.00
0.99
1.00
1.00
0.93
0.91
0.93
0.93
0.92
0.92
0.93
0.93
0.93
0.92
0.93
0.93
0.93
0.93
F(A,B)4(A,B)N(F,B)
CD5AA
CE3AA
FC4(B,C)N(F,B)
FG3AAA
FK4(C,D)NF
CK3BA
CK5A/CK5BA
CK5A/CK5BT
CK5A/CK5BW
FK4(C,D)NB
COILS + 315(A,J)AV048090 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AC
CD5AA
042
048
048
042
048
042
048
042
048
042
042
048
0.99
0.98
1.00
0.99
1.00
0.99
1.00
0.99
1.00
0.99
0.99
1.00
0.94
0.92
0.94
0.93
0.94
0.93
0.94
0.93
0.94
0.93
0.93
0.94
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
CE3AA
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
042
048
042
048
048
042
048
042
048
042
048
042
048
048
0.99
0.98
0.99
1.00
1.00
0.99
1.00
0.99
1.00
0.99
1.00
0.99
1.00
1.00
0.92
0.91
0.93
0.92
0.92
0.92
0.93
0.92
0.92
0.92
0.92
0.92
0.92
0.92
CK3BA
CK5A/CK5BA
CD5AA
CE3AA
CK5A/CK5BE
CK5A/CK5BT
CK3BA
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CK5A/CK5BA
CK5A/CK5BT
CK5A/CK5BW
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
042
048
042
048
0.99
0.98
0.99
1.00
0.93
0.91
0.93
0.93
See notes on page 24.
—20—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
Total
Total
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
System
System
CFM
1225
1400
1575
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C042-C, D Outdoor Section With CC5A/CD5AA042 Indoor Section continued
72
67
62
57
72
67
62
57
72
67
62
57
45.2
41.2
37.4
35.9
22.4
28.3
34.0
35.9
4.01
3.89
3.77
3.72
4.10
3.98
3.86
3.83
4.19
4.06
3.95
3.94
42.6
38.8
35.3
34.2
43.3
39.5
36.1
35.5
43.8
40.0
36.7
36.6
21.4
27.4
32.9
34.2
4.25
4.11
3.97
3.93
40.1
36.6
33.2
32.5
20.5
26.4
31.8
32.5
4.48
4.33
4.18
4.15
37.6
34.3
31.1
30.8
19.6
25.5
30.6
30.8
4.72
4.55
4.39
4.38
4.82
4.65
4.51
4.51
4.90
4.74
4.63
4.63
35.1
32.0
29.1
29.1
18.7
24.6
29.1
29.1
4.95
4.77
4.60
4.59
5.05
4.87
4.74
4.73
5.14
4.96
4.86
4.85
46.0
42.0
38.2
37.3
23.4
30.1
36.2
37.3
22.4
29.1
35.0
35.5
4.34
4.20
4.08
4.05
40.6
37.1
34.0
33.7
21.4
28.1
33.7
33.7
4.57
4.43
4.30
4.28
38.1
34.8
31.9
31.9
20.6
27.2
31.9
31.9
35.5
32.4
30.1
30.1
19.7
26.3
30.1
30.1
46.5
42.5
38.9
38.5
24.3
31.7
38.1
38.5
23.3
30.7
36.6
36.6
4.43
4.29
4.17
4.16
41.2
37.5
34.8
34.7
22.4
29.7
34.8
34.7
4.67
4.52
4.40
4.40
38.4
35.1
32.8
32.8
21.4
28.8
32.8
32.8
35.8
32.6
30.9
30.9
20.6
27.8
30.9
30.9
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Unit
Size
Indoor
Unit
Size
042
048
Section
Capacity
Power
Section
Capacity
1.00
1.00
Power
0.96
0.96
COILS + 355MAV042060 VARIABLE-SPEED FURNACE
CK5A/CK5BA
CK3BA
CK5A/CK5BN
042
042
1.00
0.97
0.96
0.96
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CK3BA
042
042
048
042
048
1.01
1.00
1.00
1.00
1.00
0.93
0.94
0.94
0.94
0.94
CC5A/CD5AA
CK3BA
042
042
048
042
048
1.01
1.00
1.00
1.00
1.00
0.93
0.95
0.95
0.95
0.95
CK5A/CK5BA
CK5A/CK5BA
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CK3BA
042
042
048
048
1.00
1.00
1.00
1.00
0.94
0.94
0.94
0.94
CK3BA
042
048
—
1.00
1.00
—
0.96
0.96
—
CK5A/CK5BW
See notes on page 24.
—21—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
MBtuh†
115
Capacity
MBtuh†
125
Capacity
Total
Total
System
Total
System
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
System
System
CFM
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C048-C Outdoor Section With CC5A/CD5AA048 Indoor Section
72
67
62
57
72
67
62
57
72
67
62
57
54.9
50.1
45.6
43.5
55.6
50.8
46.3
44.7
56.2
51.4
46.8
45.8
27.0
34.1
41.0
43.5
27.9
35.6
42.9
44.7
28.7
37.0
44.7
45.8
4.53
4.42
4.33
4.29
4.61
4.50
4.40
4.37
4.69
4.57
4.47
4.45
52.6
47.9
43.6
41.9
53.2
48.6
44.2
43.1
53.8
49.1
44.7
44.1
26.2
33.2
40.0
41.9
27.0
34.7
41.9
43.1
27.8
36.1
43.5
44.1
4.93
4.81
4.72
4.68
5.01
4.89
4.79
4.76
5.08
4.96
4.86
4.85
50.1
45.7
41.5
40.3
50.7
46.2
42.1
41.4
51.2
46.7
42.6
42.3
25.3
32.3
39.0
40.3
26.1
33.7
40.7
41.4
26.9
35.1
42.2
42.3
5.37
5.25
5.14
5.11
5.44
5.32
5.22
5.20
5.52
5.40
5.29
5.28
47.5
43.3
39.3
38.6
48.1
43.8
39.9
39.6
48.5
44.2
40.5
40.4
24.3
31.3
37.8
38.6
25.2
32.8
39.4
39.6
25.9
34.2
40.5
40.4
5.85
5.72
5.60
5.58
5.92
5.80
5.68
5.67
6.00
5.87
5.76
5.76
44.8
40.8
37.1
36.8
45.3
41.2
37.7
37.7
45.7
41.6
38.5
38.5
23.4
30.3
36.5
36.8
24.2
31.8
37.7
37.7
24.9
33.1
38.5
38.5
6.36
6.22
6.09
6.07
6.44
6.29
6.17
6.17
6.51
6.37
6.26
6.26
1450
1600
1750
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Unit
Indoor
Unit
Size
Section
Size
060
048
048
060
048
048
060
048
048
060
048
060
048
060
048
060
048
060
070
048
060
054
070
048
060
006
005
Capacity
1.00
0.98
1.00
1.03
1.00
1.01
1.04
1.00
1.00
1.00
1.00
1.00
0.97
1.00
1.00
1.03
1.01
1.04
1.04
1.01
1.03
1.04
1.04
1.00
1.03
1.04
1.03
Power
1.00
0.99
1.00
1.01
1.00
1.00
1.02
0.99
1.00
1.01
1.00
1.01
0.98
1.01
1.00
1.01
1.02
1.05
1.02
1.02
1.04
1.02
1.02
1.00
1.01
0.95
0.96
Section
Capacity
0.98
1.00
0.98
1.00
0.98
1.00
0.98
1.01
Power
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
CK3BA
048
060
048
060
048
060
048
060
0.93
0.93
0.93
0.93
0.93
0.93
0.93
0.92
CK5A/CK5BA
CK5A/CK5BT
CD5AA
CE3AA
CK5A/CK5BW
CK5A/CK5BX
CF5AA
CK3BA
COILS + 315(A,J)AV066135 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
060
048
048
060
048
048
060
048
060
048
060
048
060
048
060
0.99
0.98
0.98
1.00
0.98
0.98
1.00
0.98
1.00
0.98
1.00
0.98
1.00
0.98
1.01
0.94
0.94
0.93
0.93
0.93
0.93
0.93
0.93
0.93
0.93
0.93
0.93
0.93
0.93
0.92
CK5A/CK5BA
CK5A/CK5BN
CD5AA
CE3AA
CK5A/CK5BW
CK5A/CK5BX
F(A,B)4A(A,B)N(F,B)
CK3BA
FB4(A,B)NB
FC4(B,C)N(F,B)
CK5A/CK5BA
CK5A/CK5BT
FC4(B,C)NB
FG3AAA
CK5A/CK5BW
CK5A/CK5BX
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
FK4(C,D)NB
FK4(C,D)NF
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
060
048
048
060
048
048
060
048
060
048
060
048
060
048
060
—
0.99
0.98
0.98
1.00
0.98
0.98
1.00
0.98
1.00
0.98
1.00
0.98
1.00
0.98
1.01
—
0.93
0.93
0.93
0.92
0.93
0.93
0.92
0.93
0.92
0.93
0.92
0.93
0.92
0.93
0.92
—
COILS + 315(A,J)AV048090 VARIABLE-SPEED FURNACE
CC5A/CD5AC
CD5AA
048
048
048
060
048
048
048
0.98
0.98
0.98
1.00
0.98
0.98
0.98
0.95
0.95
0.95
0.94
0.95
0.95
0.95
CD5AA
CE3AA
CE3AA
CK3BA
CK5A/CK5BA
CK5A/CK5BT
CK3BA
CK5A/CK5BA
CK5A/CK5BT
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
CD5AA
060
048
048
048
048
060
0.99
0.98
0.98
0.98
0.98
1.00
0.94
0.94
0.93
0.93
0.93
0.92
CK5A/CK5BW
CK5A/CK5BX
CE3AA
See notes on page 24.
—22—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
MBtuh†
115
Capacity
MBtuh†
125
Capacity
Total
Total
System
Total
System
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
System
System
CFM
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C048-C Outdoor Section With CC5A/CD5AA048 Indoor Section continued
72
67
62
57
72
67
62
57
72
67
62
57
54.9
50.1
45.6
43.5
55.6
50.8
46.3
44.7
56.2
51.4
46.8
45.8
27.0
34.1
41.0
43.5
27.9
35.6
42.9
44.7
28.7
37.0
44.7
45.8
4.53
4.42
4.33
4.29
4.61
4.50
4.40
4.37
4.69
4.57
4.47
4.45
52.6
47.9
43.6
41.9
53.2
48.6
44.2
43.1
53.8
49.1
44.7
44.1
26.2
33.2
40.0
41.9
27.0
34.7
41.9
43.1
27.8
36.1
43.5
44.1
4.93
4.81
4.72
4.68
5.01
4.89
4.79
4.76
5.08
4.96
4.86
4.85
50.1
45.7
41.5
40.3
50.7
46.2
42.1
41.4
51.2
46.7
42.6
42.3
25.3
32.3
39.0
40.3
26.1
33.7
40.7
41.4
26.9
35.1
42.2
42.3
5.37
5.25
5.14
5.11
5.44
5.32
5.22
5.20
5.52
5.40
5.29
5.28
47.5
43.3
39.3
38.6
48.1
43.8
39.9
39.6
48.5
44.2
40.5
40.4
24.3
31.3
37.8
38.6
25.2
32.8
39.4
39.6
25.9
34.2
40.5
40.4
5.85
5.72
5.60
5.58
5.92
5.80
5.68
5.67
6.00
5.87
5.76
5.76
44.8
40.8
37.1
36.8
45.3
41.2
37.7
37.7
45.7
41.6
38.5
38.5
23.4
30.3
36.5
36.8
24.2
31.8
37.7
37.7
24.9
33.1
38.5
38.5
6.36
6.22
6.09
6.07
6.44
6.29
6.17
6.17
6.51
6.37
6.26
6.26
1450
1600
1750
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Unit
Size
Indoor
Unit
Size
Section
Capacity
Power
Section
Capacity
0.98
0.99
0.98
0.99
Power
COILS + 355MAV042080 VARIABLE-SPEED FURNACE
CJ5A/CK5AA
048
060
048
060
060
060
0.98
0.96
0.98
0.96
0.96
0.97
CK3BA
CK5A/CK5BA
048
060
048
0.98
0.99
0.98
0.97
0.98
0.97
CK3BA
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
CK5A/CK5BN
CK5A/CK5BX
0.99
1.02
CK3BA
060
060
060
060
0.99
0.99
0.99
1.02
0.98
0.98
0.98
0.98
CK5A/CK5BA
CK5A/CK5BN
CK5A/CK5BX
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
CK3BA
048
060
060
048
060
0.98
0.99
0.99
0.98
1.02
0.96
0.96
0.96
0.96
0.96
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
CK5A/CK5BA
CK5A/CK5BW
CK5A/CK5BX
CC5A/CD5AW
060
—
1.01
—
0.95
—
See notes on page 24.
—23—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
MBtuh†
115
Capacity
MBtuh†
125
Capacity
Total
Total
System
Total
System
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
System
System
CFM
EWB
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
Total Sens‡ kW**
593C060-C Outdoor Section With CC5A/CD5AW060 Indoor Section
72
67
62
57
72
67
62
57
72
67
62
57
66.9
61.1
55.7
53.2
68.1
62.3
56.8
55.2
69.0
63.1
57.7
56.9
33.0
41.8
50.3
53.2
34.5
44.2
53.4
55.2
35.8
46.6
56.2
56.9
5.85
5.70
5.56
5.50
5.98
5.82
5.69
5.65
6.10
5.95
5.81
5.79
63.9
58.3
53.1
51.3
64.9
59.3
54.1
53.1
65.7
60.1
55.0
54.7
31.9
40.6
49.0
51.3
33.3
43.0
52.0
53.1
34.7
45.4
54.5
54.7
6.39
6.23
6.08
6.03
6.52
6.35
6.21
6.18
6.64
6.48
6.33
6.32
60.7
55.4
50.4
49.1
61.6
56.2
51.3
50.8
62.3
56.9
52.3
52.3
30.7
39.4
47.6
49.1
32.1
41.8
50.4
50.8
33.4
44.1
52.3
52.3
6.97
6.80
6.65
6.61
7.11
6.93
6.78
6.76
7.23
7.05
6.90
6.91
57.3
52.3
47.5
46.7
58.1
53.0
48.5
48.4
58.7
53.6
49.7
49.7
29.5
38.1
46.0
46.7
30.9
40.5
48.4
48.4
32.2
42.8
49.7
49.7
7.61
7.43
7.25
7.22
7.74
7.56
7.39
7.39
7.87
7.68
7.54
7.54
53.8
48.9
44.0
43.8
54.4
49.5
45.5
45.4
55.0
50.0
46.8
46.8
28.2
36.8
43.8
43.8
29.6
39.2
45.5
45.4
30.9
41.5
46.8
46.8
8.29
8.09
7.86
7.86
8.43
8.22
8.04
8.04
8.55
8.35
8.21
8.21
1750
2000
2250
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Unit
Indoor
Unit
Size
060
060
Section
Size
060
060
060
060
060
060
060
060
070
060
070
060
006
Capacity
0.96
1.00
1.01
0.96
0.96
0.96
1.00
1.01
1.03
1.01
1.03
0.99
1.02
Power
0.98
1.00
1.00
0.98
0.98
0.99
1.00
1.04
1.02
1.04
1.02
0.99
0.98
Section
Capacity
0.97
0.98
Power
0.95
0.93
CC5A/CD5AA
CC5A/CD5AW
CE3AA
CK5A/CK5BT
CK5A/CK5BX
COILS + 315(A,J)AV066135 VARIABLE-SPEED FURNACE
CK3BA
CC5A/CD5AA
CC5A/CD5AW
CE3AA
0.96
0.97
0.98
0.97
0.97
0.97
0.98
0.95
0.94
0.95
0.95
0.95
0.95
0.93
060
060
060
060
060
060
060
CK5A/CK5BA
CK5A/CK5BN
CK5A/CK5BX
F(A,B)4(A,B)N(F,B)
FB4(A,B)NB
FC4(B,C)N(F,B)
FC4(B,C)NB
FG3AAA
CK3BA
CK5A/CK5BA
CK5A/CK5BT
CK5A/CK5BX
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AW
CE3AA
0.96
0.97
0.98
0.97
0.97
0.97
0.98
0.94
0.94
0.94
0.95
0.95
0.95
0.93
060
060
060
060
060
060
060
FK4(C,D)NB
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CC5A/CD5AA
CE3AA
CK3BA
CK5A/CK5BA
0.96
0.98
0.97
0.97
0.95
0.94
0.95
0.95
CK3BA
060
060
060
060
CK5A/CK5BA
CK5A/CK5BT
CK5A/CK5BX
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at same elevation per ARI standard 210/240-94. If additional tubing length and/or indoor
unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F entering air at the indoor coil. For sensible capacities at other than 80°F, deduct 835 Btuh per 1000 CFM of
indoor coil air for each degree below 80°F, or add 835 Btuh per 1000 CFM of indoor coil air per degree above 80°F. When the required data falls between
the published data, interpolation may be performed.
** Unit kW is total of indoor and outdoor unit kilowatts.
—24—
CONDENSER ONLY RATINGS*
CONDENSER ENTERING AIR TEMPERATURES °F
SST
°F
55
65
75
85
95
105
115
593C018-C, D
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
17.9
75.7
1.10
19.8
77.7
1.13
21.8
79.9
1.15
24.0
82.3
1.18
26.3
84.9
1.20
28.6
87.6
1.23
16.6
84.2
1.18
18.5
86.2
1.22
20.5
88.3
1.25
22.6
90.4
1.28
24.8
92.8
1.31
27.1
95.3
1.35
15.3
93.0
1.26
17.1
94.8
1.30
19.0
96.8
1.34
21.0
98.9
1.38
23.2
101.0
1.42
25.4
103.0
1.46
14.0
102.0
1.33
15.7
104.0
1.38
17.6
105.0
1.43
19.5
107.0
1.48
21.6
110.0
1.53
23.7
112.0
1.58
12.7
111.0
1.39
14.3
112.0
1.45
16.1
114.0
1.51
17.9
116.0
1.57
19.9
118.0
1.63
22.0
120.0
1.69
11.3
120.0
1.44
12.9
121.0
1.51
14.6
123.0
1.58
16.4
125.0
1.65
18.2
127.0
1.72
20.2
129.0
1.79
10.0
129.0
1.46
11.5
130.0
1.55
13.1
132.0
1.64
14.8
134.0
1.72
16.6
135.0
1.80
18.5
137.0
1.88
30
35
40
45
50
55
593C024-C, D
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
24.0
81.3
1.52
26.6
83.6
1.57
29.4
86.2
1.61
32.3
88.9
1.66
35.3
92.0
1.71
38.4
95.3
1.76
22.3
89.8
1.63
24.8
91.9
1.68
27.5
94.3
1.74
30.3
96.8
1.79
33.2
99.5
1.85
36.3
102.0
1.91
20.5
98.6
1.73
22.9
101.0
1.79
25.5
103.0
1.86
28.2
105.0
1.92
31.1
108.0
1.99
34.1
110.0
2.06
18.7
108.0
1.81
21.0
109.0
1.89
23.5
111.0
1.97
26.1
114.0
2.05
28.8
116.0
2.12
31.7
118.0
2.20
16.9
117.0
1.88
19.2
118.0
1.97
21.5
120.0
2.06
24.0
122.0
2.15
26.6
124.0
2.25
29.4
127.0
2.34
15.1
126.0
1.93
17.3
127.0
2.04
19.5
129.0
2.14
21.9
131.0
2.25
24.4
133.0
2.35
27.0
135.0
2.46
13.3
136.0
1.96
15.4
137.0
2.08
17.6
138.0
2.20
19.8
140.0
2.32
22.2
141.0
2.44
24.7
144.0
2.56
30
35
40
45
50
55
593C030-C, D
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
30.2
81.3
1.88
33.5
83.4
1.93
37.1
85.7
1.99
40.8
88.1
2.04
44.8
90.7
2.09
49.0
93.5
2.14
27.9
90.5
2.02
31.0
92.5
2.09
34.4
94.7
2.16
38.0
97.0
2.23
41.7
99.5
2.29
45.7
102.0
2.36
25.6
99.8
2.15
28.6
102.0
2.24
31.8
104.0
2.32
35.2
106.0
2.41
38.8
108.0
2.49
42.6
111.0
2.57
23.4
109.0
2.27
26.3
111.0
2.37
29.3
113.0
2.47
32.5
115.0
2.57
35.9
117.0
2.67
39.5
120.0
2.77
21.3
118.0
2.36
24.0
120.0
2.48
26.8
122.0
2.59
29.8
124.0
2.71
33.0
126.0
2.83
36.4
129.0
2.94
19.3
128.0
2.44
21.8
129.0
2.57
24.5
131.0
2.70
27.3
133.0
2.84
30.3
135.0
2.97
33.5
137.0
3.10
17.3
137.0
2.50
19.7
139.0
2.65
22.2
140.0
2.79
24.8
142.0
2.94
27.6
144.0
3.09
30.6
146.0
3.25
30
35
40
45
50
55
593C036-C, D
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
35.9
80.5
2.20
39.7
82.6
2.25
43.8
84.8
2.30
48.1
87.2
2.35
33.4
89.7
2.38
37.1
91.6
2.45
41.0
93.7
2.52
45.1
96.0
2.59
30.9
98.9
2.55
34.4
101.0
2.64
38.1
103.0
2.72
42.1
105.0
2.81
28.4
108.0
2.70
31.7
110.0
2.80
35.3
112.0
2.91
39.1
114.0
3.02
25.9
118.0
2.82
29.1
119.0
2.95
32.5
121.0
3.08
36.1
123.0
3.20
23.4
127.0
2.93
26.5
128.0
3.07
29.7
130.0
3.22
33.1
132.0
3.37
21.0
136.0
3.00
23.9
138.0
3.17
27.0
139.0
3.34
30.2
141.0
3.51
30
35
40
45
50
TCG
SDT
KW
52.6
89.7
2.40
49.5
98.4
2.66
46.3
107.0
2.90
43.1
116.0
3.12
39.9
125.0
3.33
36.7
134.0
3.52
33.6
143.0
3.68
TCG
SDT
KW
57.4
92.4
2.45
54.0
101.0
2.72
50.7
110.0
2.98
47.3
119.0
3.23
43.9
127.0
3.46
40.5
136.0
3.66
37.2
145.0
3.85
55
See notes on page 26.
—25—
CONDENSER ONLY RATINGS* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
SST
°F
55
65
75
85
95
105
115
593C042-C, D
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
40.6
81.5
2.56
44.8
83.7
2.63
49.3
86.1
2.69
54.0
88.7
2.76
58.9
91.4
2.82
64.1
94.3
2.89
37.9
90.4
2.76
42.0
92.5
2.85
46.3
94.8
2.93
50.9
97.2
3.02
55.7
99.8
3.10
60.7
103.0
3.19
35.2
99.4
2.94
39.2
101.0
3.05
43.3
104.0
3.16
47.7
106.0
3.26
52.3
108.0
3.37
57.1
111.0
3.48
32.5
108.0
3.10
36.3
110.0
3.23
40.3
112.0
3.36
44.5
115.0
3.49
48.9
117.0
3.62
53.6
120.0
3.75
29.7
118.0
3.23
33.4
119.0
3.38
37.2
121.0
3.54
41.2
123.0
3.69
45.5
126.0
3.85
49.9
128.0
4.00
26.9
127.0
3.33
30.4
128.0
3.51
34.1
130.0
3.69
38.0
132.0
3.87
42.0
134.0
4.04
46.3
137.0
4.22
24.1
136.0
3.43
27.5
137.0
3.64
31.0
139.0
3.84
34.7
141.0
4.04
38.6
143.0
4.24
42.7
145.0
4.44
30
35
40
45
50
55
593C048-C
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
44.5
80.0
2.76
48.7
81.8
2.81
53.1
83.7
2.86
57.8
85.8
2.92
62.7
88.0
2.99
67.9
90.4
3.06
42.6
89.8
3.03
46.7
91.5
3.09
50.9
93.3
3.14
55.5
95.3
3.20
60.2
97.4
3.27
65.3
99.8
3.35
40.6
99.6
3.34
44.5
101.0
3.39
48.7
103.0
3.45
53.1
105.0
3.52
57.7
107.0
3.59
62.5
109.0
3.67
38.5
109.0
3.68
42.3
111.0
3.74
46.4
113.0
3.80
50.6
115.0
3.87
55.0
117.0
3.95
59.7
119.0
4.03
36.4
119.0
4.05
40.1
121.0
4.12
43.9
123.0
4.19
48.0
124.0
4.26
52.3
126.0
4.34
56.8
128.0
4.42
34.2
129.0
4.45
37.7
131.0
4.53
41.4
132.0
4.60
45.3
134.0
4.68
49.4
136.0
4.77
53.7
138.0
4.86
31.9
139.0
4.87
35.2
140.0
4.96
38.8
142.0
5.05
42.5
144.0
5.14
46.5
146.0
5.24
50.6
147.0
5.33
30
35
40
45
50
55
593C060-C
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
55.9
84.5
3.47
61.1
86.7
3.54
66.6
89.0
3.63
72.3
91.4
3.72
78.3
94.1
3.82
84.7
96.8
3.93
53.4
94.2
3.82
58.4
96.4
3.90
63.7
98.7
3.99
69.3
101.0
4.09
75.1
104.0
4.20
81.2
106.0
4.31
50.9
104.0
4.22
55.7
106.0
4.31
60.8
108.0
4.40
66.1
111.0
4.50
71.8
113.0
4.62
77.6
116.0
4.74
48.2
114.0
4.65
52.8
116.0
4.75
57.7
118.0
4.85
62.8
120.0
4.96
68.3
123.0
5.08
73.9
125.0
5.21
45.4
124.0
5.13
49.8
126.0
5.23
54.5
128.0
5.35
59.5
130.0
5.47
64.7
132.0
5.59
70.1
135.0
5.73
42.5
134.0
5.64
46.7
136.0
5.75
51.2
138.0
5.88
56.0
140.0
6.01
60.9
142.0
6.15
66.1
144.0
6.29
39.5
143.0
6.16
43.5
145.0
6.31
47.8
147.0
6.45
52.4
150.0
6.60
57.1
152.0
6.75
62.0
154.0
6.91
30
35
40
45
50
55
* ARI listing applies only to systems shown in Ratings and Performance table.
KW — Total Power (kW)
SDT — Saturated Temperature Leaving Compressor (°F)
SST — Saturated Temperature Entering Compressor (°F)
TCG — Gross Cooling Capacity (1000 Btuh)
—26—
SYSTEM DESIGN
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature without low ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature is 125°F (51.7°C).
4. For reliable operation, unit should be level in all horizontal planes.
5. Maximum elevation of indoor coil above or below base of outdoor unit is: Indoor coil above = 50 ft indoor coil below = 150 ft. (See items 6 and 7
following.)
6. For interconnecting refrigerant tube lengths of 50 to 175 ft or 20 ft vertical differential, consult Long-Line Application Guideline available from
equipment distributor.
7. Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft.
8. If any refrigerant tubing is buried, provide a minimum 6-in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in.
may be buried without further consideration. For buried lines longer than 3 ft, consult your local distributor.
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
10. Mismatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.
—27—
Air-Cooled, Split-System
Air Conditioner
GUIDE SPECIFICATIONS
593C
1-1/2 to 5 Tons Nominal
Condenser fan motors will be totally enclosed, 1-phase type with
class B insulation and permanently lubricated bearings.
GENERAL
System Description
Shafts will be corrosion resistant.
Outdoor-mounted, air-cooled, split-system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a her-
metic compressor, an air-cooled coil, propeller-type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with steel wire safety
guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Quality Assurance
Unit will be rated in accordance with the latest edition of ARI
Standard 240.
Condenser coil will be air cooled.
Unit will be certified for capacity and efficiency, and listed in the
latest ARI directory.
Coil will be constructed of aluminum fins mechanically bonded to
copper tubes which are then cleaned, dehydrated, and sealed.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Refrigeration Components
Refrigeration circuit components will include liquid-line shutoff
valve with sweat connections, suction tube shutoff valves with
sweat connections, system charge of R-22 (R-410A) refrigerant,
and compressor oil.
Unit will be constructed in accordance with UL standards and will
carry the UL label of approval. Unit will have c-UL approval.
Unit cabinet will be capable of withstanding Federal Test Method
Standard No. 141 (Method 6061) 500-hr salt spray test.
Operating Characteristics
Air-Cooled condenser coils will be leak tested at 150 psig and
pressure tested at 300 psig.
The capacity of the unit will meet or exceed
suction temperature of
load will not exceed
Btuh at a
°F. The power consumption at full
kw.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Combination of the unit and the evaporator or fan coil unit will
have a total net cooling capacity of Btuh or greater at con-
ditions of
CFM entering air temperature at the evaporator
Warranty (for inclusion by specifying engineer)
at
°F wet bulb and
°F.
°F dry bulb, and air entering the
U.S. and Canada only.
unit at
PRODUCTS
Equipment
The system will have an SEER of
DOE conditions.
Btuh/watt or greater at
Factory assembled, single piece, air-cooled air conditioner unit.
Contained within the unit enclosure will be all factory wiring, pip-
ing, controls, compressor, refrigerant charge (R-22), and special
features required prior to field start-up.
Electrical Requirements
Nominal unit electrical characteristics will be
phase, 60 hz. The unit will be capable of satisfactory operation
within voltage limits of v to v.
v, 1 single
Unit Cabinet
Unit electrical power will be single point connection.
Control circuit will be 24v.
Unit cabinet will be constructed of galvanized steel, bonderized,
and coated with a powder coat paint.
Special Features
Fans
Refer to section of this literature identifying accessories and de-
scriptions for specific features and available enhancements.
Condenser fan will be direct-drive propeller type, discharging air
upward.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Cancels: PDS 593C.18.6
© 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231
PRINTED IN U.S.A.
Catalog No. 5259-301
2-03
—28—
|